Plan Review Notes
Plan Review Notes For Permit 06030341
Permit Number 06030341
Review Stop P
Sequence Number 5
Notes
Date Text
2006-10-21 10:14:30PLUMBING REVISIONS
 DENIED;
 1.PAGE P-1 REVISION 1 AND 2 WERE DELETED FROM NEW PLAN,
 (ADA REQUIREMENTS FOR BREAK SINK PLEASE PUT BACK ON
 PLAN.
 2.PAGE P-1 CHANGES MADE ON PLANS AND NOT CLOUDED; (A)
 AIR ADMITTANCE VALVE AT HAND SINK, THE ADV MUST COMPLY
 WITH
 FBC-2004 PLUMBING SECTION 917.3.1. (B)ADDITION OF
 MOP SINK AND LAVATORY IN CLOSET. (C) MOVED LOCATION OF
 LAVATORY
 IN ADA BATHROOM. (D) DELETED 2" VENT UP. (E) DELETED
 FSC BOX LOCATIONS.
 3.PAGE P-2 (OWNERS CHANGES 10-2-06) (A) TANKLESS WATER
 HEATER ADDED PLEASE DELETE WATER HEATER SCHEMATIC.
 ELECTRICAL REVISION REQUIRED
 (B) EXISTING FLOOR DRAIN DELETED.
 4.NEW SANITARY AND WATER RISER DIAGRAMS REQUIRED
 SHOWING CHANGES MADE IN THE PLUMBING SYSTEM.
 5. PAGE P-2 HOT WATER REQUIRED TO MOP SINK SECTION
 607.1.
 6. THE VENT AND DRAIN PIPES FOR VACUUM EQUIPMENT IS NOT
 SHOWN ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695