Plan Review Notes
Plan Review Notes For Permit 06030341
Permit Number 06030341
Review Stop MEDGAS
Sequence Number 3
Notes
Date Text
2006-06-22 00:00:00DENIED;
 PLEASE USE NFPA 99C 2002 ADITION CHAPTER
 5, LEVEL 3 PIPING FOR VACUUM AND
 COMPRESSORS.
 SEC.5.3.10.1. WILL LIST THE PIPING
 MATERIAL PERMITED TO BE USED.
 SEC.5.3.10.3. LISTS THE EXCEPTED
 FITTINGS AND HOW THEY ARE INSTALL ONTO
 THE PIPE.
 IF COPPER TUBING AND FITTING ARE BRAZED
 SEE SEC.5.3.10.7.
 YOU CAN ALSO CONTACT THE EQUIPMENT
 COMPANIES FOR SIZING AND MATERIAL
 REQUIREMENTS FOR THEIR EQUIPMENT.
 COLLECTOR TANK DRAIN TAIL PEACE CAN BE
 NO LONGER THAN 2' AND THE TRAP MUST B3E
 SERVICEABLE. SEE ATTACHED COPY OF
 FIG.A.5.3.3.6.3(B).
 MED GAS REVIEW BY;
 JOHN LEECH
 805-6695