Date Text
2006-05-30 00:00:00DENIED;
 1.BREAK SINK; SUPPORTS FOR TOE PLATE
 MUST BE REMOVABLE ALSO. SHOW DETAIL OF
 REMOVABLE FRONT TO AVOID PROBLEMS DURING
 CONSTUCTION.
 2.DEPTH OF BREAK SINK;
 PAGE AN-1PLUMBING SCHEDULE STILL SHOWS
 SINK AT 8" MUST BE A MAX. OF 6 1/2"
 DEEP.
 3.( SECOND REQUEST) DRINKING FOUNTAIN IS
 REQUIRED TABLE 403.1. FIRST DRINKING
 FOUNTAIN IS REQUIRED TO BE INSTALLED TO
 THE PLUMBING SYSTEM. SEE FBC-2004
 PLUMBING SEC 410.1.
 4.(SECOND REQUEST) WATER HAMMER ARRESTOR
 TO BE INSTALLED WHERE QUICK CLOSING
 VALVES ARE INSTALLED. SEC.604.9.
 5.(SECOND REQUEST)RISER DIAGRAMS
 REQUIRED, SANITARY, WATER AND MED-GAS.
 AMENDMENTS TO THE BUILDING CODE CHAPTER
 1, SEC. 106.3.5.1.3(13).
 6.WATER HEATER DIAGRAM; SHOW MEANS OF
 THERMAL EXPANTION PROTECTION PER SEC
 607.3.