Plan Review Notes
Plan Review Notes For Permit 06030341
Permit Number 06030341
Review Stop MEDGAS
Sequence Number 2
Notes
Date Text
2006-05-30 00:00:00DENIED;
 1.(SECOND REQUEST) ADD TO NOTES;
 LICENSED MED-GAS CONTRACTOR REQUIRED TO
 INSTALL VACUUM AND COMPRESSED AIR LINES.
 SEPARATE PERMIT REQUIRED.
 2.AIR COMPRESSOR DETAIL; DELETE LAST 1/2
 OF MAKE UP AIR NOTE."TO NEAREST RETURN
 AIR DUCT".
 3.COMPRESSOR DETAIL; 1/2" SUPPLY AIR
 LINES ARE SHOWN, FLAT DRAWING SHOWS 1"
 LINES. PLEASE CLEARLY SHOW PIPE SIZE TO
 BE USED ON A RISER DIAGRAM.
 4. VACUUM PUMP DETAIL; DISCHARGE FROM
 COLLECTION TANK SHALL BE DIRECT PER.
 FBC-2004 PLUMBING SEC. 713.7.
 MED-GAS REVIEW BY;
 JOHN LEECH
 805-6695