| Plan Review Notes For Permit 06030341 |
| Permit Number |
06030341 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-30 00:00:00 | DENIED; | | | 1.(SECOND REQUEST) ADD TO NOTES; | | | LICENSED MED-GAS CONTRACTOR REQUIRED TO | | | INSTALL VACUUM AND COMPRESSED AIR LINES. | | | SEPARATE PERMIT REQUIRED. | | | 2.AIR COMPRESSOR DETAIL; DELETE LAST 1/2 | | | OF MAKE UP AIR NOTE."TO NEAREST RETURN | | | AIR DUCT". | | | 3.COMPRESSOR DETAIL; 1/2" SUPPLY AIR | | | LINES ARE SHOWN, FLAT DRAWING SHOWS 1" | | | LINES. PLEASE CLEARLY SHOW PIPE SIZE TO | | | BE USED ON A RISER DIAGRAM. | | | 4. VACUUM PUMP DETAIL; DISCHARGE FROM | | | COLLECTION TANK SHALL BE DIRECT PER. | | | FBC-2004 PLUMBING SEC. 713.7. | | | MED-GAS REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|