| Plan Review Notes For Permit 06030341 |
| Permit Number |
06030341 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-30 00:00:00 | *** DENIED *** | | | 1) RETURN AIR TRANSFER DUCT TO | | | CONSULTATION ROOM IS TO SMALL, SEE NOTE | | | #3. | | | | | | 2) PLEASE SHOW ON MECHANICAL PLANS HOW | | | OUTSIDE AIR WILL BE GETTING TO AHU. | | | | | | 3)BALANCED RETURN AIR. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. PER 2004 | | | FBC/M 601.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|