| Plan Review Notes For Permit 06030341 |
| Permit Number |
06030341 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-03 00:00:00 | DENIED; | | | 1.BREAK SINK; SHOW FRONTAL, CLEAR FLOOR | | | SPACE ON FLOOR PLAN. SEC11-47.24.3. | | | IN-SINKERATOR CANNOT BE INSTALLED ON | | | SINK BECAUSE OF KNEE CLEARANCE. SEC. | | | 11-24..3. | | | THE DEPTH OF SINK IS A MAX. OF 6 1/2". | | | SEC.11-24.4. PLEASE CHANGE PLUMBING | | | SCHEDULE ON PAGE AN1. | | | ADD NOTE THAT EXPOSED PIPES TO BE | | | INSULATED. | | | 2.A DRINKING FOUINTAIN IS REQUIRED. | | | FBC-2004 PLUMBING TABLE 403.1, ALSO SEE | | | SEC. 410.1. | | | 3.SIZE AND LOCATION OF WATER HEATER, NOT | | | SHOWN ON DRAWINGS. ALSO LIST ON PLUMBING | | | SCHEDULE. | | | 4.WATER HAMMER ARRESTORS TO BE INSTALLED | | | WHERE EVER QUICK-CLOSING VALVES ARE | | | INSTALLED. SEC. 604.9 SEE PAGE P-2 WATER | | | SOLENOID SCHEMATIC. | | | 5.RISER DIAGRAMS REQUIRED WATER AND | | | SANITARY. AMENDMENTS TO THE FLORIDA | | | BUILDING CODE CHAPTER 1, 2004 EDITTION | | | SEC. 106.3.5.1.3(13). | | | 6.STERILIZERS TO BE INDIRECT WASTED MUST | | | COMPLY WITH SEC.713.3 AND VENT SIZE TO | | | COMPLY WITH TABLE 713.11.1 | | | 7.THE PLANS MUST BE DRAWN BY A DESIGN | | | PROFESSIONAL, PER 481 FS AND SIGNED AND | | | SEALED PER. 481 FS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|