Plan Review Notes
Plan Review Notes For Permit 06030341
Permit Number 06030341
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-03 00:00:00DENIED;
 1.BREAK SINK; SHOW FRONTAL, CLEAR FLOOR
 SPACE ON FLOOR PLAN. SEC11-47.24.3.
 IN-SINKERATOR CANNOT BE INSTALLED ON
 SINK BECAUSE OF KNEE CLEARANCE. SEC.
 11-24..3.
 THE DEPTH OF SINK IS A MAX. OF 6 1/2".
 SEC.11-24.4. PLEASE CHANGE PLUMBING
 SCHEDULE ON PAGE AN1.
 ADD NOTE THAT EXPOSED PIPES TO BE
 INSULATED.
 2.A DRINKING FOUINTAIN IS REQUIRED.
 FBC-2004 PLUMBING TABLE 403.1, ALSO SEE
 SEC. 410.1.
 3.SIZE AND LOCATION OF WATER HEATER, NOT
 SHOWN ON DRAWINGS. ALSO LIST ON PLUMBING
 SCHEDULE.
 4.WATER HAMMER ARRESTORS TO BE INSTALLED
 WHERE EVER QUICK-CLOSING VALVES ARE
 INSTALLED. SEC. 604.9 SEE PAGE P-2 WATER
 SOLENOID SCHEMATIC.
 5.RISER DIAGRAMS REQUIRED WATER AND
 SANITARY. AMENDMENTS TO THE FLORIDA
 BUILDING CODE CHAPTER 1, 2004 EDITTION
 SEC. 106.3.5.1.3(13).
 6.STERILIZERS TO BE INDIRECT WASTED MUST
 COMPLY WITH SEC.713.3 AND VENT SIZE TO
 COMPLY WITH TABLE 713.11.1
 7.THE PLANS MUST BE DRAWN BY A DESIGN
 PROFESSIONAL, PER 481 FS AND SIGNED AND
 SEALED PER. 481 FS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695