| 2006-03-30 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE PLANS MUST BE DRAWN BY A DESIGN | | | PROFESSIONAL PER 481 FS AND SIGNED AND | | | SEALED PER 481 FS. | | | | | | 1} PROVIDE A PANEL SCHEDULE OR SCHEDULES | | | INDICATING ALL CIRCUITS IN THE AREA OF | | | WORK AND RATINGS OF PANELS. | | | | | | 2} SUBMIT A LOAD CALCULATION PER 106 FBC | | | AND 215.5 NEC. | | | | | | 3} INDICATE CIRCUIT NUMBERS AT ALL | | | LIGHTS AND DEVICES THAT BRANCH CIRCUIT | | | AND ARTICLE 700. | | | | | | 4} INDICATE LOCATIONS OF ALL EXIT AND | | | EMERGENCY LIGHTING. | | | | | | 5} LABEL REQUIRED GFI RECEPTACLES PER | | | 210.8 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|