2006-03-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE PLANS MUST BE DRAWN BY A DESIGN
 PROFESSIONAL PER 481 FS AND SIGNED AND
 SEALED PER 481 FS.
  
 1} PROVIDE A PANEL SCHEDULE OR SCHEDULES
 INDICATING ALL CIRCUITS IN THE AREA OF
 WORK AND RATINGS OF PANELS.
  
 2} SUBMIT A LOAD CALCULATION PER 106 FBC
 AND 215.5 NEC.
  
 3} INDICATE CIRCUIT NUMBERS AT ALL
 LIGHTS AND DEVICES THAT BRANCH CIRCUIT
 AND ARTICLE 700.
  
 4} INDICATE LOCATIONS OF ALL EXIT AND
 EMERGENCY LIGHTING.
  
 5} LABEL REQUIRED GFI RECEPTACLES PER
 210.8 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  