| 2006-03-17 00:00:00 | *** UNSAT *** |
| | |
| | 1)NOTE: PLEASE SEE EXISTING PANEL |
| | INDICATES AHU'S #1 AND #2 AS 10KW UNITS |
| | WITH 1-POLE OCP?? PLEASE KNOW, EVEN IF |
| | THIS SI EXISITNG? THIS WILL BE REQUIRED |
| | TO BE BROUGHT UP TO CODE AS IT VIOLATE'S |
| | MANY NEC ARTICLES AND PROMOTES A LIFE |
| | SAFETY AND PROPERTY HAZARD. |
| | 240.4,424.3,310.16 ETC ETC. |
| | |
| | 2)NOTE: PELASE SEE FBC 2004 CHAPTER 13, |
| | FOR COMMERCIAL BLDGS. 13-415.1.ABC.1.1 |
| | &.2,13-415.1.ABC.3 PROVIDE DETAILED |
| | INFORMATION ON TYOE OF LT FIXTURES. |
| | PLEASE SEE THE NEW REQUIREMENTS FOR THE |
| | NEW ENERGY CODE. |
| | |
| | 3)NOTE: PLEASE MAKE REFERENCE TO 605, |
| | 605.6 ON PLANS FOR INSTALLATIONS OF |
| | FURNITURE. |
| | |
| | 4)NOTE: PLEASE SEE PLANS SHALL DICTATE |
| | THE CURRENT CODES IN EFFECT. 2002 |
| | NFPA-70, 2003 NFPA-101,2002 NFPA-72. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | ONLY ONE COPY OF THE REMOVED OLD/VOIDED |
| | SHEETS SHOULD BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |