| 2006-09-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06030337 |
| | ADD: 1617 N. FLAGLER DR |
| | CONT: AQUATIC SPECIALTIES INC. |
| | TEL: (954)346-3316 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THIS SAME ISSUE WAS BROUGHT IN UNDER |
| | THE MASTER PERMIT (05061170) THE |
| | DESCRIPTION OF WORK TO REMODEL POOL AND |
| | ADD A "DECO-DRAIN" TO STORM. |
| | THERE WAS A REVISION TO COVER THE |
| | DECO-DRAIN WITH A MARBLE OR TRAVATINE, |
| | THIS REVISION WAS DENIED BECAUSE OF FBC |
| | 424.1.3.1.2. THE CODE INDICATES SLOPE IS |
| | TO BE AWAY FROM THE POOL OR TO DECK |
| | DRAINS TO PREVENT STANDING WATER. THE |
| | PLANS ALSO INDICATE THE USAGE OF A CURB |
| | THAT WILL ALLOW FOR STANDING WATER ON |
| | THE POOL DECK. THIS IS WHERE A |
| | DECO-DRAIN WILL BE REQUIRED TO PREVENT |
| | STANDING WATER ON THE POOL DECK. |
| | |
| | THE NEW PERMIT NUMBER AND |
| | DESCRIPTION OF WORK IS FOR DECK-DRAIN |
| | INSTALLATION. THIS DEPICTION INDICATES |
| | 4 1/4" HOLES AT 10" O.C. TRUE THIS WILL |
| | DRAIN WATER BUT ISN'T IN COMPLIANCE WITH |
| | CHAPTER 11 FLORIDA ACCESSIBILITY CODE. |
| | 11-4.5 GROUND AND FLOOR SURFACES. |
| | THERE ARE TWO SECTIONS THAT APPEAR TO |
| | DEAL WITH THIS CONCERN, SEE LISTING |
| | BELOW. |
| | |
| | 11-4.5.4 GRATINGS. |
| | IF GRATINGS ARE LOCATED IN WALKING |
| | SURFACES, THEN THEY SHALL HAVE SPACES NO |
| | GREATER THAN ? INCH (13 MM) WIDE IN ONE |
| | DIRECTION [SEE FIGURE 11-8 (G)]. IF |
| | GRATINGS HAVE ELONGATED OPENINGS, THEN |
| | THEY SHALL BE PLACED SO THAT THE LONG |
| | DIMENSION IS PERPENDICULAR TO THE |
| | DOMINANT DIRECTION OF TRAVEL [SEE FIGURE |
| | 11-8 (H)]. |
| | |
| | 11-4.5.2 CHANGES IN LEVEL. |
| | CHANGES IN LEVEL UP TO ? INCHES (6 MM) |
| | MAY BE VERTICAL AND WITHOUT EDGE |
| | TREATMENT [SEE FIGURE 11-7 (C)]. CHANGES |
| | IN LEVEL BETWEEN ? INCH AND ? INCH (6 MM |
| | AND 13 MM) SHALL BE BEVELED WITH A SLOPE |
| | NO GREATER THAN 1:2 [SEE FIGURE 11-7 |
| | (D)]. CHANGES IN LEVEL GREATER THAN ? |
| | INCH (13 MM) SHALL BE ACCOMPLISHED BY |
| | MEANS OF A RAMP THAT COMPLIES WITH |
| | SECTION 11-4.7 OR 11-4.8 . |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |