| Plan Review Notes For Permit 06030268 |
| Permit Number |
06030268 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-18 00:00:00 | | | | FAILED | | | SAME NOTES AS PREVIOUS REVIEW (3.20.06), | | | PLEASE SEE THAT MR SINCLAIR GETS AN | | | OPPORTUNITY TO SEE THE COMMENTS BEFORE | | | RESUBMITTING | | | | | | THE PLAN INDICATES 3-#4 CU FEEDERS TO | | | THE POOL PANEL. THE CALCULATION PROVIDED | | | BYTHE ELECTRICAL CONTRACTOR INDICATES A | | | 30 AMP FEED TO A POOL PANEL. PLEASE | | | CORRELATE. | | | | | | NOTE #1 AT THE ELECTRICAL SCHEMATIC | | | REFERENCES THE 2005 NEC. PLEASE NOTE THE | | | STATE HAS NOT YET ADOPTED 2005 AND WE | | | ARE CURRENTLY ENFORCING 2002 NEC. | | | | | | DIFFERENTCOMMENT FROM THIS REVIEW, | | | THERE IS A HEATER (PRESUMABLY ELECTRIC) | | | ON THE ELECTRICAL SCHEMATIC THAT SHOULD | | | BE REMOVED . IF THE HEATER IS GAS THERE | | | SHOULD ONLY BE AN IGNITOR INDICATED IF | | | 120V. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|