| Plan Review Notes For Permit 06030268 |
| Permit Number |
06030268 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-20 00:00:00 | | | | FAILED | | | | | | THE PLAN INDICATES 3-#4 CU FEDERS TO THE | | | POOL PANEL. THE CALCULATION PROVIDED BY | | | THE ELECTRICAL CONTRACTOR INDICATES A 30 | | | AMP FEEDTO A POOL PANEL. PLEASE | | | CORRELATE. | | | | | | NOTE #1 AT THE ELECTRICAL SCHEMATIC | | | REFERENCES THE 2005 NEC. PLEASE NOTE THE | | | STATE HAS NOT YET ADOPTED 2005 AND WE | | | ARE CURRENTLY ENFORCING 2002 NEC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|