| Date |
Text |
| 2006-04-21 00:00:00 | |
| | 1) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORIC SURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) 104.6.5 BUILDING PERMIT VALUATION. IF |
| | IN THE OPINION OF THE BUILDING OFFICIAL |
| | THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED ESTIMATES |
| | AND/OR BONA FIDED SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION FOR |
| | BUILDINGS AND SYSTEMS SHALL BE FOUND IN |
| | MARSHALL AND |
| | SWIFT OR THE SOUTHERN BUILDING CODE |
| | CONGRESS INTERNATIONAL VALUATION TABLES, |
| | LATEST EDITION, AND SHALL BE BASED ON |
| | TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN |
| | FEES, OVERHEAD AND PROFIT, EXCLUDING |
| | ONLY LAND VALUE. |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE ACTUAL PERMIT PLANS |
| | MUST BE STAMPED BY THAT OFFICE, AND A |
| | COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION.PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 5) 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1. GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 |
| | FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| | PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | 6) THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMMENDMENT TO FBC 106.3.3 PRODUCT |
| | APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE |
| | REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. PRODUCT APPROVAL |
| | REQUIRED FOR EXTERIOR DOORS/WINDOWS/ |
| | ROOFING PRODUCTS/SHUTTERS/ |
| | ETC.TWO COPIES OF EACH PRODUCT IS |
| | REQUIRED FOR PLAN REVIEW. |
| | |
| | 7) TRUSS DESIGN |
| | R802.10.1 TRUSS DESIGN DRAWINGS. |
| | TRUSS DESIGN DRAWINGS, PREPARED IN |
| | CONFORMANCE WITH SECTION R802.10.1 , |
| | SHALL BE PROVIDED TO THE BUILDING |
| | OFFICIAL AND APPROVED PRIOR TO |
| | INSTALLATION. TRUSS DESIGN DRAWINGS |
| | SHALL INCLUDE, AT A MINIMUM, THE |
| | INFORMATION SPECIFIED BELOW. TRUSS |
| | DESIGN DRAWING SHALL BE PROVIDED WITH |
| | THE SHIPMENT OF TRUSSES DELIVERED TO THE |
| | JOBSITE. |
| | |
| | 8)ENERGY CALCULATIONS NEED TO BE ON FORM |
| | 600A-04 (2004) PER FBC 13-600.3.A. |
| | THESE FORMS SHALL BE SINGED AND DATED BY |
| | THE OWNER/AGENT. |
| | |
| | 9) STATE THE CORRECT MEAN ROOF HEIGHT ON |
| | THE DRAWINGS (SHEET A-2). ONLY THE |
| | PERSON WHO SIGN AND SEAL THE DRAWINGS |
| | ARE ALLOWED TO MAKE CHANGES TO THEM. SEE |
| | SHEET A-2 WHERE THE WORD SCREENED WAS |
| | SCRATCHED OUT. THE ARCHITECT WILL HAVE |
| | TO SIGN AND DATE EACH HAND WRITTEN |
| | CHANGE MADE OR SUBMIT A COMPLETE SET OF |
| | NEW DRAWINGS WITH CHANGES. |
| | |
| | 10) ON SHEET S-1 THE TRUSS DESIGN |
| | CRITERIA MENTION THE 2001 FL BLDG CODE. |
| | NOTE: WE ARE UNDER THE 2004 BLDG CODE. |
| | PLEASE CORRECT THIS INFORMATION. WHERE |
| | IS DETAIL #3 ON SHEET S-4? |
| | |
| | 11) SHEET S-4 THE DETAIL FOR THE FLOOR |
| | JOIST INDICATE A SIMPSON LUS26 WHICH HAS |
| | A WIDTH OF (1 9/16") IF THE FLOOR JOISTS |
| | ARE (2) 2X12. HOW WILL THE LUS26 WORK? |
| | PLEASE CLARIFY, AND SHOW THE CORRECT |
| | STRAP. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | FAX:(561)805-6731 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |