| 2006-03-27 00:00:00 | DENIED |
| | |
| | 1) PLANS SPECIFY THE EXISTING BUILDING |
| | TYPE AS TYPE IIA, UNPROTECTED. ACCORDING |
| | TO 2004 FBC TABLE 601 A TYPE IIA |
| | BUILDING IS ESSENTIALLY ONE HOUR |
| | PROTECTED. PLEASE CLARIFY. IS THE SPACE |
| | FIRE SPRINKLERED? |
| | |
| | 2) THE SCOPE OF WORK IS TO OPEN THE WALL |
| | BETWEEN TWO TENANT SPACES CREATING ONE |
| | LARGE SPACE. PROVIDE A DRAWING OF THE |
| | EXISTING SPACE WITH THE DIMENSIONS AND |
| | OCCUPANT LOADS FOR THE COMBINED SPACES. |
| | INDICATE THE EXISTS AND PATHS OF TRAVEL |
| | FOR THE COMBINED SPACE. |
| | |
| | 3) SPECIFY ON PLANS THAT THE ALTERATIONS |
| | TO THE PRIMARY FUNCTION AREA COMPLY WITH |
| | FLORIDA ACCESIBILITY CODE AS REQUIRED BY |
| | 2004 FBC 11-4.1.6. |
| | |
| | 11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |