| Plan Review Notes For Permit 06030125 |
| Permit Number |
06030125 |
|
| Review Stop |
B1 |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-09 00:00:00 | OKAY TO PUT AN "N" PER LUIS MARTINEZ | | 2006-03-03 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- CITY POLICY REQUIRES PRE-INSPECTION | | | FOR ROOF OVER PERMITS TO VERIFY | | | COMPLIANCE WITH SEC. 1510 FBC 2004. | | | APPLICATION WAS SENT TO THE CHIEF | | | BUILDING INSPECTOR FOR PRE-INSPECTION. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 2- CALCULATIONS SUBMITTED: | | | A) CALCULATIONS TO BE DONE BY | | | QUALIFIED PROFESSIONAL AND THEY MUST BE | | | SIGNED AND SEALED AS REQUIRED BY CHAPTER | | | 471 OR 481 FLORIDA STATUTES. | | | | | | B) CONTRACTOR INFORMATION ON | | | CALCULATIONS SUBMITTED IS DIFFERENT THAN | | | CONTRACTOR INFORMATION SUBMITTED FOR | | | PERMIT. REVISE AS REQUIRED. | | | | | | C) CALCULATIONS TO BE SPECIFIC WITH | | | ASCE 7 EDITION USED. SEE FBC 2004 FOR | | | PROPER EDITION TO BE USED. | | | | | | 3- FROM DADE COUNTY NOA PROVIDED SPECIFY | | | APPROVED ASSEMBLY THAT IS GOING TO BE | | | INSTALLED. SEE CITY POLICY FOR | | | RE-ROOFING PERMITS. SEE ATTACHED COPY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|