Plan Review Notes
Plan Review Notes For Permit 06030125
Permit Number 06030125
Review Stop B1
Sequence Number 1
Notes
Date Text
2006-03-09 00:00:00OKAY TO PUT AN "N" PER LUIS MARTINEZ
2006-03-03 00:00:00BUILDING REVIEW CHECKLIST:
 1- CITY POLICY REQUIRES PRE-INSPECTION
 FOR ROOF OVER PERMITS TO VERIFY
 COMPLIANCE WITH SEC. 1510 FBC 2004.
 APPLICATION WAS SENT TO THE CHIEF
 BUILDING INSPECTOR FOR PRE-INSPECTION.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- CALCULATIONS SUBMITTED:
 A) CALCULATIONS TO BE DONE BY
 QUALIFIED PROFESSIONAL AND THEY MUST BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER
 471 OR 481 FLORIDA STATUTES.
  
 B) CONTRACTOR INFORMATION ON
 CALCULATIONS SUBMITTED IS DIFFERENT THAN
 CONTRACTOR INFORMATION SUBMITTED FOR
 PERMIT. REVISE AS REQUIRED.
  
 C) CALCULATIONS TO BE SPECIFIC WITH
 ASCE 7 EDITION USED. SEE FBC 2004 FOR
 PROPER EDITION TO BE USED.
  
 3- FROM DADE COUNTY NOA PROVIDED SPECIFY
 APPROVED ASSEMBLY THAT IS GOING TO BE
 INSTALLED. SEE CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712