| 2006-03-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- ENGINEERING CALCULATIONS COMMENTS: |
| | A) PAGE 6 OF 6 OF ENGINEERING CALCS |
| | SPECIFIES THE SAME NUMBER AND TYPE OF |
| | FASTENERS AS SHOWN ON PAGE 6 OF 9 OF |
| | DADE COUNTY NOA #02-1219.01 FOR |
| | INSULATED SYSTEM IN WOOD DECK. ACCORDING |
| | TO THE NOA THIS FASTENING IS DESIGNED |
| | FOR A MAX. DESIGN PRESSURE OF -60PSF. |
| | |
| | ENGINEER TO REVIEW PRODUCT APPROVAL AND |
| | SEE GENERAL LIMITATION #7 TO PROVIDE THE |
| | CORRECT CALCULATIONS REQUIRED TO ENHANCE |
| | THE UPLIFT CAPACITY OF THE ROOF SYSTEM. |
| | |
| | B) THERE IS A DADE COUNTY NOA AND AN |
| | ENGINEER'S REPORT SUBMITTED FOR THIS |
| | TYPE OF ROOF. NEED TO PROVIDE ONLY THE |
| | INFORMATION THAT WAS SUBMITTED TO OBTAIN |
| | THE FLORIDA PRODUCT APPROVAL FL1559-R3. |
| | GO TOWEBSITE WWW.FLORIDABUILDING.ORG |
| | TO DOWNLOAD THE SAME INFORMATION THAT |
| | WAS SUBMITTED FOR FLORIDA PRODUCT |
| | APPROVAL. DON'T MIS MATCH DADE COUNTY |
| | NOA'S AND ENGINEER'S REPORTS. |
| | |
| | C) REVISE ENGINEERING CALCULATIONS. |
| | INFORMATION SUBMITTED IS NOT RELEVANT TO |
| | THE ROOFING CALCS REQUIRED FOR THE |
| | ENHANCING OF THE ROOF SYSTEM AND IS ALSO |
| | INCORRECT: |
| | 1) THIS IS NOT RESIDENTIAL GROUP. |
| | 2) WHAT'S THE TYPE OF CONSTRUCTION? |
| | 3) LIVE LOADS FOR OTHER THAN ROOF IS |
| | IRRELEVANT. |
| | 4) WIND LOADS ARE BASED ON ASCE 7-02, |
| | NOT ASCE 7-98. SEE FBC 2004. |
| | 5) TOPOGRAPHIC FACTOR INFORMATION IS |
| | INCORRECT. |
| | 6- FBC 2004. REVISE ORIGINAL SHEET. |
| | DON'T CROSS OUT BY HAND FBC 2001. |
| | |
| | D) ENGINEER TO SIGN, SEAL AND DATE |
| | EVERY SHEET AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES AND FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 2- WIND UPLIFT PRESSURE CALCULATIONS FOR |
| | ROOFS NEED TO HAVE ENGINEER'S ORIGINAL |
| | SEAL, SIGNATURE AND DATE. ALSO, ENGINEER |
| | TO PROVIDE ALL HIS INFORMATION AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTES |
| | |
| | 3- CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO |
| | BE INSTALLED. INSULATED OR NON-INSULATED |
| | SYSTEM. |
| | |