| Plan Review Notes For Permit 06030124 |
| Permit Number |
06030124 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-07 00:00:00 | *** DENIED *** | | | 1) ENERGY CALAULATIONS SUBMITTED WITH | | | BUILDING PERMIT IS CALLING FOR 28,000 | | | TOTAL BTU'S, PLANS SUBMITTED ARE CALLING | | | FOR 31,200 TOTAL BTU'S. THE PLANS CAN | | | NOT CALL FOR MORE THAN THE ENERGY CAL'S. | | | PLEASE CORRECT. | | | | | | 2) PLANS ARE CALLING FOR MORE SENSIBLE | | | BTU'S THAN THE MANUAL J CAL. WILL ALLOW | | | PLEASE CORRECT. | | | | | | 3) PLEASE SHOW THE COPPER LINE SIZES, | | | AND THE CONDENSATE DRAIN LINE LOCATION | | | ON THE MECHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|