2007-08-06 15:59:10** MECHANICAL REVISION **
 *** DENIED ***
 1) THE DEFLECT-O ADJUSTABLE DIFFUSER SUBMITTED IS NOT
 STATE THAT IT IS DESIGNED TO BE A CLOTHES DRYER VENT
 CAP, PLEASE SUBMIT THE CLOTHES DRYER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS SHOWING THAT THIS TYPE OF CAP
 MAY BE USED ON THEIR DRYER EXHAUST, AND INFORMATION
 FROM DEFLECT-O SHOWING THAT IT IS UL APPROVED AS A
 CLOTHES DRYER VENT CAP, SEE 2004 FBC M1501.1.
  
 **2004 FBC/R M1501.1 GENERAL.
 DRYER EXHAUST SYSTEMS SHALL BE INDEPENDENT OF ALL OTHER
 SYSTEMS, SHALL CONVEY THE MOISTURE TO THE OUTDOORS AND
 SHALL TERMINATE ON THE OUTSIDE OF THE BUILDING. EXHAUST
 DUCT TERMINATIONS SHALL BE IN ACCORDANCE WITH THE DRYER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. SCREENS SHALL
 NOT BE INSTALLED AT THE DUCT TERMINATION. EXHAUST DUCTS
 SHALL NOT BE CONNECTED WITH SHEET-METAL SCREWS OR
 FASTENING MEANS WHICH EXTEND INTO THE DUCT. EXHAUST
 DUCTS SHALL BE EQUIPPED WITH A BACKDRAFT DAMPER.
 EXHAUST DUCTS SHALL BE CONSTRUCTED OF MINIMUM
 0.016-INCH-THICK (0.406 MM) RIGID METAL DUCTS, HAVING
 SMOOTH INTERIOR SURFACES WITH JOINTS RUNNING IN THE
 DIRECTION OF AIR FLOW. FLEXIBLE TRANSITION DUCTS USED
 TO CONNECT THE DRYER TO THE EXHAUST DUCT SYSTEM SHALL
 BE LIMITED TO SINGLE LENGTHS, NOT TO EXCEED 8 FEET
 (2438 MM) IN LENGTH AND SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH UL 2158A. TRANSITION DUCTS SHALL NOT BE
 CONCEALED WITHIN CONSTRUCTION.
  