| Plan Review Notes For Permit 06030119 |
| Permit Number |
06030119 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-07-25 08:34:34 | ** MECHANICAL REVISION ** | | | *** DENIED *** | | | 1) PLANS PAGE M-1 SHOWS THE RANGE HOOD VENT AND THE | | | CLOTHES DRYER VENT TERMINATING AT THE SOFFIT, PLEASE | | | SHOW A DETAIL HOW THIS IS BEING INSTALLED AND SUBMIT A | | | MANUFACTURERS SPECIFICATION SHEET FOR THE END CAP THAT | | | IS BEING USED, SEE 2004 FBC/R M1501.1 SCREENS SHALL NOT | | | BE INSTALLED AT DUCT TERMINATION AND SHALL BE EQUIPPED | | | WITH A BACKDRAFT DAMPER. | | | | | | 2) SEE YELLOW HIGH LIGHTS ON PLANS PAGE M-2 SHOWING | | | RETURN AIR DUCTS THAT NEED TO BE SIZED. | | | | | | 3) PAGE M-2 SHOWS ONLY ONE 8" RETURN AIR DUCT TO AHU-1 | | | AND ONE 10" RETURN AIR DUCT TO AHU-2 IF THIS IS THE | | | ONLY MEANS OF RETURN TO THE AIR HANDLERS THAT WOULD PUT | | | THEM AT A VELOCITY OF 4000 AND 2600, IF THIS IS THE | | | CASE PLEASE SUBMIT MANUAL D CALCULATIONS, DETAILED | | | MANUFACTURER'S SPECIFICATION'S FOR THE AIR HANDLER WITH | | | COOLING COIL, AND FLEX DUCTS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|