Plan Review Notes
Plan Review Notes For Permit 06030119
Permit Number 06030119
Review Stop M
Sequence Number 4
Notes
Date Text
2007-07-25 08:34:34** MECHANICAL REVISION **
 *** DENIED ***
 1) PLANS PAGE M-1 SHOWS THE RANGE HOOD VENT AND THE
 CLOTHES DRYER VENT TERMINATING AT THE SOFFIT, PLEASE
 SHOW A DETAIL HOW THIS IS BEING INSTALLED AND SUBMIT A
 MANUFACTURERS SPECIFICATION SHEET FOR THE END CAP THAT
 IS BEING USED, SEE 2004 FBC/R M1501.1 SCREENS SHALL NOT
 BE INSTALLED AT DUCT TERMINATION AND SHALL BE EQUIPPED
 WITH A BACKDRAFT DAMPER.
  
 2) SEE YELLOW HIGH LIGHTS ON PLANS PAGE M-2 SHOWING
 RETURN AIR DUCTS THAT NEED TO BE SIZED.
  
 3) PAGE M-2 SHOWS ONLY ONE 8" RETURN AIR DUCT TO AHU-1
 AND ONE 10" RETURN AIR DUCT TO AHU-2 IF THIS IS THE
 ONLY MEANS OF RETURN TO THE AIR HANDLERS THAT WOULD PUT
 THEM AT A VELOCITY OF 4000 AND 2600, IF THIS IS THE
 CASE PLEASE SUBMIT MANUAL D CALCULATIONS, DETAILED
 MANUFACTURER'S SPECIFICATION'S FOR THE AIR HANDLER WITH
 COOLING COIL, AND FLEX DUCTS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.