Plan Review Notes
Plan Review Notes For Permit 06030119
Permit Number 06030119
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-08 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 84,000 TOTAL BTU'S, MECHANICAL PLANS ARE
 CALLING FOR 90,000 TOTAL BTU'S. THE
 PLANS CAN NOT CALL FOR MORE THAN THE
 ENERGY CAL'S, PLEASE CORRECT.
  
 2) THE MANUAL J IS CALLING FOR A TOTAL
 SENSIBLE BTU'S OF 56,203 AND THE MECH.
 PLANS ARE CALLING FOR A TOTAL SENSIBLE
 BTU'S OF 68,800. THE PLANS CAN ONLY CALL
 FOR 20% MORE THAN THE MANUAL J, PER 2004
 FBC 13-607.1.ABC.1.1 .PLEASE CORRECT.
  
 3) PLEASE SUBMIT MANUAL J (LONG FORM)
 SHOWING DUCT SIZES AND CFM'S FOR EACH
 ROOM. AS MECH. PLAN DUCT (FLEX) SIZES
 AND CFM'S SHOWING WILL CAUSE TO LOW AN
 AIR VELOCITY.
  
 4) PROVIDE RETURN AIR FOR THE OFFICE AND
 LIVING ROOM, SEE NOTE #6.
  
 5) TRANSFER RETURN AIR DUCTS (FLEX) ON
 SECOND FLOOR, NEED TO SHOW SIZES, SEE
 NOTE #6.
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 7) PLEASE SHOW LOCATION AND SIZES OF
 MAIN RETURN AIR GRILLS TO AIR HANDLERS.
  
 8) PLEASE SHOW LOCATION OF DRYER VENT ON
 MECH. PLANS.
  
 9) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS FIRE PLACE.
  
 10) PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS ON MECHANICAL PLANS, FOR
 GAS FIRE PLACE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  
  