| 2006-03-08 00:00:00 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS ARE CALLING FOR |
| | 84,000 TOTAL BTU'S, MECHANICAL PLANS ARE |
| | CALLING FOR 90,000 TOTAL BTU'S. THE |
| | PLANS CAN NOT CALL FOR MORE THAN THE |
| | ENERGY CAL'S, PLEASE CORRECT. |
| | |
| | 2) THE MANUAL J IS CALLING FOR A TOTAL |
| | SENSIBLE BTU'S OF 56,203 AND THE MECH. |
| | PLANS ARE CALLING FOR A TOTAL SENSIBLE |
| | BTU'S OF 68,800. THE PLANS CAN ONLY CALL |
| | FOR 20% MORE THAN THE MANUAL J, PER 2004 |
| | FBC 13-607.1.ABC.1.1 .PLEASE CORRECT. |
| | |
| | 3) PLEASE SUBMIT MANUAL J (LONG FORM) |
| | SHOWING DUCT SIZES AND CFM'S FOR EACH |
| | ROOM. AS MECH. PLAN DUCT (FLEX) SIZES |
| | AND CFM'S SHOWING WILL CAUSE TO LOW AN |
| | AIR VELOCITY. |
| | |
| | 4) PROVIDE RETURN AIR FOR THE OFFICE AND |
| | LIVING ROOM, SEE NOTE #6. |
| | |
| | 5) TRANSFER RETURN AIR DUCTS (FLEX) ON |
| | SECOND FLOOR, NEED TO SHOW SIZES, SEE |
| | NOTE #6. |
| | |
| | 6) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 7) PLEASE SHOW LOCATION AND SIZES OF |
| | MAIN RETURN AIR GRILLS TO AIR HANDLERS. |
| | |
| | 8) PLEASE SHOW LOCATION OF DRYER VENT ON |
| | MECH. PLANS. |
| | |
| | 9) PLEASE SUBMIT DETAILED MANUFACTURE'S |
| | SPECIFICATION'S AND INSTALLATION |
| | INSTRUCTIONS FOR GAS FIRE PLACE. |
| | |
| | 10) PLEASE PROVIDE COMBUSTION AIR |
| | CALCULATIONS ON MECHANICAL PLANS, FOR |
| | GAS FIRE PLACE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |
| | |
| | |