| 2006-03-22 00:00:00 | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE RISER DIAGRAM INDICATES A |
| | METER/MAIN AND TWO PANELS. THE PLAN |
| | INDICATES A METER AND THREE PANELS, |
| | PLEASE CORRELATE. |
| | |
| | 2} PANELS #2 & 3 ARE SHOWN AS MLO. |
| | CONDUCTORS ENERING SEPARATE STRUCTURES |
| | MUST HAVE A DISCONNECTING MEANS PER |
| | 225.31 AN BE GROUNDED PER 250.32. THE |
| | RISER AN DPANEL SCHEDULE ARE NOT IN |
| | COMPLIANCE. |
| | |
| | 3} THE 1/0 SERVICE CONDUCTORSINDICATED |
| | ON THE RISER TO FPL ARE TOO SMALL FOR A |
| | 400 AMP SERVICE PER 310.15(B)(6). |
| | |
| | 4} THE PANEL MARKED #1 HAS CIRCUITS |
| | 1'3'5'AND 7 ON A COMMON TRIP BREAKER |
| | WITH ONLY ONE 10K LOAD INDICATED FOR TWO |
| | AHU'S. |
| | |
| | 5} CIRCUITS 2&4, PANEL #1 SHOWS #14 WIRE |
| | ON A 50 AMP BREAKER. SEE 310.16. |
| | |
| | 6} THE MINIMUM GROUNDING ELECTRODE |
| | CONDUCTOR FOR A 400 AMP SERVICE IS 1/0 |
| | CU PER 250.66. SEE RISER. |
| | |
| | 7} THE ELEVATOR SHOWN ON THE PLAN IS NOT |
| | IN THE LOAD CALCULATION OR ON A PANEL |
| | SCHEDULE . PLEASE INDICATE ALL EQUIPMENT |
| | ON THE PLAN. |
| | |
| | 8} THE ROOMS ON THE FIRST AND SECOND |
| | FLOOR, EXCEPT THE BATHS AND SITTING |
| | ROOM, ALL NEED RECEPTACLES ADDED TO |
| | COMPLY WITH THE SPACING REQUIREMENTS OF |
| | 210.52(A)(1)&(2). SEE REVIEWED PLAN FOR |
| | SOME REDLINED AREAS. |
| | |
| | 9} THE ATTIC AREA USED AS MECHANICAL |
| | SPACE MUST HAVE LIGHT PER 210.70(A)(3) |
| | AND RECEPTACLES PER 210.63. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |