 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM INDICATES A
 METER/MAIN AND TWO PANELS. THE PLAN
 INDICATES A METER AND THREE PANELS,
 PLEASE CORRELATE.
  
 2} PANELS #2 & 3 ARE SHOWN AS MLO.
 CONDUCTORS ENERING SEPARATE STRUCTURES
 MUST HAVE A DISCONNECTING MEANS PER
 225.31 AN BE GROUNDED PER 250.32. THE
 RISER AN DPANEL SCHEDULE ARE NOT IN
 COMPLIANCE.
  
 3} THE 1/0 SERVICE CONDUCTORSINDICATED
 ON THE RISER TO FPL ARE TOO SMALL FOR A
 400 AMP SERVICE PER 310.15(B)(6).
  
 4} THE PANEL MARKED #1 HAS CIRCUITS
 1'3'5'AND 7 ON A COMMON TRIP BREAKER
 WITH ONLY ONE 10K LOAD INDICATED FOR TWO
 AHU'S.
  
 5} CIRCUITS 2&4, PANEL #1 SHOWS #14 WIRE
 ON A 50 AMP BREAKER. SEE 310.16.
  
 6} THE MINIMUM GROUNDING ELECTRODE
 CONDUCTOR FOR A 400 AMP SERVICE IS 1/0
 CU PER 250.66. SEE RISER.
  
 7} THE ELEVATOR SHOWN ON THE PLAN IS NOT
 IN THE LOAD CALCULATION OR ON A PANEL
 SCHEDULE . PLEASE INDICATE ALL EQUIPMENT
 ON THE PLAN.
  
 8} THE ROOMS ON THE FIRST AND SECOND
 FLOOR, EXCEPT THE BATHS AND SITTING
 ROOM, ALL NEED RECEPTACLES ADDED TO
 COMPLY WITH THE SPACING REQUIREMENTS OF
 210.52(A)(1)&(2). SEE REVIEWED PLAN FOR
 SOME REDLINED AREAS.
  
 9} THE ATTIC AREA USED AS MECHANICAL
 SPACE MUST HAVE LIGHT PER 210.70(A)(3)
 AND RECEPTACLES PER 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW