| 2006-08-07 00:00:00 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE COMPLETE PANEL LOADS ON |
| | SUB PANEL SPLP. |
| | PLEASE SEE 220.12B FOR LOADS FOR TRACK |
| | LIGHTING. PELAS ADJUST CIRCUITING AS |
| | NEEDED. |
| | 220, 215.3, 215.5 |
| | |
| | 2) NOTE: PLEASE SEE SPLP, NOW MENTIONS A |
| | "SERVER" AND SHOWS THIS IS MAY APPEAR TO |
| | BE AN "IT" ROOM. PLEASE SEE NEC 645 IF |
| | THIS ROOM IS AN IT ROOM. PLEASE SEE |
| | NFPA-75. PLEASE SPECIFY ON PLANS IF NOT |
| | AN IT ROOM AND DOES NT MEET NFPA-75 |
| | REQUIREMENTS. |
| | |
| | 3) NOTE: PLEASE SE SPLP SHOWS A LOADOF |
| | 6.5 A'S FOR CIRCUITS #2, UNCLEAR WHERE |
| | THIS LOAD COMES FROM AT THIS TIME AS |
| | THIS IS A DEDICATED CIRCUIT UNLESS THIS |
| | ALSO FEEDS SOMETHING ELSE. |
| | |
| | 4) NOTE: PLEASE SEE VALUE FOR INCREASED |
| | SCOPE OF WORK SHALL BE ADJUSTED. PLEASE |
| | ALSO SEE THE ORIGINAL APPLIED VALUE WAS |
| | 137K . |
| | FBC 108.3 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |