| 2006-06-01 00:00:00 | IN ELEC FOR REVIEW. |
| | ********* UNSAT ************ |
| | |
| | |
| | ** PLEASE SEE SOME ITEMS FROM FIRST |
| | REVIEW AND NEW ITEMS DUE TO CHANGEES IN |
| | PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS REFERENCE |
| | "PALM BEACH COUNTY LOCAL AMENDMENTS" ON |
| | E.0. PLEASE KNOW, THIS WORK IS LOCATED |
| | IN THE CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SEE A VD CALCULATION WAS |
| | PROVIDED FOR THE MAIN SEC'S, HOWEVER |
| | COULD NOT LOCATE ANY WORST CASE FOR |
| | BRANCH CIRCUITS PER FBC CHAPTER 13, |
| | 13-413.1ABC.1.2 |
| | |
| | 3) NOTE: PLEASE SEE A COMPLETELY NEW |
| | SERVICE IS NOT SHOWN, PLEASE CLARIFY |
| | "GUTTER" NOW SHOWN ON THE LOAD SIDE OF |
| | THE METER AND NEW MAIN? |
| | PLEASE SEE RISER NEEDS TO INDICATE THE |
| | EXISTING SERVICE BEING REMOVED AND NEW |
| | SERVICE ONLY. |
| | PLEASE ALSO CORRELATE WITH PLANS, AS |
| | PLANS DONOT INDICATE MAINS OR |
| | LOCATIONS. |
| | UNABLE TO VERIFY SERVICE MEETING 230.2, |
| | 230.70,230.72 ETC. |
| | |
| | 4) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL SERVICE EQUIPMENT. PLEASE SEE A NEW |
| | MAIN IS NOW SHOWN, HOWEVER NO RATING(S) |
| | ARE INDICATED. 110.9.215.5 |
| | |
| | 5) NOTE: PLEASE SEE CONNECTION LOCATIONS |
| | FOR THE GROUNDING ELECTRODE CONDUCTOR |
| | NEEDS TO BE VERIFIED AS IT IS SHOWN IN |
| | TWO LOCATIONS? |
| | PLEASE SEE 250.24B,250.6. |
| | |
| | 6) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO THE |
| | PANELS. |
| | 250.110,250.122,250.24, ETC |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS PLANS |
| | INDICATED ALL CONTINUOUS LOADS AT 125%, |
| | HOWEVER NOW THIS HAS BEEN REMOVED?? |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT |
| | 125%. |
| | 215.3,230.42 ETC. |
| | |
| | *** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | SUBMIT THE OLD/VOIDED SHEETS SEPARATELY |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |