| 2006-05-30 00:00:00 | |
| | 1) SUBMIT DRAWINGS SHOWING THE PREVIOUS |
| | LAYOUT OF THE BUILDING. SHEET'ET.1' HAS |
| | NO LAYOUT OF THE PREVIOUS DESIGN. |
| | |
| | 2) WPB AMMENDMENTSS TO FBC 106.3.3 THOSE |
| | PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FOR FURTHER |
| | INFORMATION SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTW WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. ALL STATE WIDE PRODUCT APPROVAL |
| | NEEDS THE STATE COVER SHEETS. NOTE: SOME |
| | THE PRODUCT APPROVAL SUBMITTED HAVE NO |
| | STATE COVEER SHEETS AND NEED THE |
| | APPROVAL BY THE DESIGNER IN WRITING. |
| | EACH PRODUCT APPROVAL NEEDS IT'S OWN |
| | COVER SHEET. ONE SET WILL BE FILED FOR |
| | RECORD AND THE OTHER SET WILL BE GIVEN |
| | TO THE CONTRACTOR. |
| | |
| | 3) THE DEMO NOTE "B" ON SHEET A.O STILL |
| | SHOWS THE DOORS BEING REMOVED AND THE |
| | OPENING FRAME IN COMPLETELY. THE |
| | INFORMATION NEEDS TO INDICATE THE NEW |
| | IMPACT DOORS. |
| | |
| | 4) IF THE WINDOWS AND DOORS WERE CHANGED |
| | THE PRODUCT APPROVALS SHALL BE SUBMITTED |
| | FOR REEVIEW FOR THE ONES WHICH WERE |
| | CHANGED. |
| | |
| | 5) THE LEVEL OF ALTERATION INDICATED ON |
| | THE DRAWINGS STATES LEVEL ONE. THIS IN |
| | INCORRECT. SEE FLORIDA EXISTING BUILDING |
| | CODE SEC.303 AND SEC.304 FOR THE |
| | DIFFERENT TYPES OF ALTERATIONS. |
| | |
| | 6) 11-5.2 COUNTERS AND BARS. |
| | WHERE FOOD OR DRINK IS SERVED AT |
| | COUNTERS EXCEEDING 34 INCHES (865 MM) IN |
| | HEIGHT FOR CONSUMPTION BY CUSTOMERS |
| | SEATED ON STOOLS OR STANDING AT THE |
| | COUNTER, A PORTION OF THE MAIN COUNTER |
| | WHICH IS 60 INCHES (1525 MM) IN LENGTH |
| | MINIMUM SHALL BE PROVIDED IN COMPLIANCE |
| | WITH SECTION 11-4.32 OR SERVICE SHALL BE |
| | AVAILABLE AT ACCESSIBLE TABLES WITHIN |
| | THE SAME AREA. |
| | |
| | 7) THE DOOR NUMBERS ON THE DOOR SCHEDULE |
| | AND THE FLOOR SHALL CORRESPOND WITH EACH |
| | OTHER. SOME OF THE DOORS ON THE FLOOR |
| | PLAN DON'T HAVE ANY NUMBER. ON THE |
| | SECOND FLOOR BETWEEN THE CONFERENCE |
| | ROOOM AND THE TWO OFFICES, THERE ARE TWO |
| | POCKET DOORS WHICH ARE NOT NUMBERED OR |
| | INDICATED ON THE DOOR SHCEDULE.THESE |
| | DOORS SHALL BE NOTED ON THE PLANS AND |
| | DOOR SCHEDULE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |