Plan Review Notes
Plan Review Notes For Permit 06030097
Permit Number 06030097
Review Stop B
Sequence Number 2
Notes
Date Text
2006-05-30 00:00:00 
 1) SUBMIT DRAWINGS SHOWING THE PREVIOUS
 LAYOUT OF THE BUILDING. SHEET'ET.1' HAS
 NO LAYOUT OF THE PREVIOUS DESIGN.
  
 2) WPB AMMENDMENTSS TO FBC 106.3.3 THOSE
 PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FOR FURTHER
 INFORMATION SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTW WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. ALL STATE WIDE PRODUCT APPROVAL
 NEEDS THE STATE COVER SHEETS. NOTE: SOME
 THE PRODUCT APPROVAL SUBMITTED HAVE NO
 STATE COVEER SHEETS AND NEED THE
 APPROVAL BY THE DESIGNER IN WRITING.
 EACH PRODUCT APPROVAL NEEDS IT'S OWN
 COVER SHEET. ONE SET WILL BE FILED FOR
 RECORD AND THE OTHER SET WILL BE GIVEN
 TO THE CONTRACTOR.
  
 3) THE DEMO NOTE "B" ON SHEET A.O STILL
 SHOWS THE DOORS BEING REMOVED AND THE
 OPENING FRAME IN COMPLETELY. THE
 INFORMATION NEEDS TO INDICATE THE NEW
 IMPACT DOORS.
  
 4) IF THE WINDOWS AND DOORS WERE CHANGED
 THE PRODUCT APPROVALS SHALL BE SUBMITTED
 FOR REEVIEW FOR THE ONES WHICH WERE
 CHANGED.
  
 5) THE LEVEL OF ALTERATION INDICATED ON
 THE DRAWINGS STATES LEVEL ONE. THIS IN
 INCORRECT. SEE FLORIDA EXISTING BUILDING
 CODE SEC.303 AND SEC.304 FOR THE
 DIFFERENT TYPES OF ALTERATIONS.
  
 6) 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34 INCHES (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH
 MINIMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.
  
 7) THE DOOR NUMBERS ON THE DOOR SCHEDULE
 AND THE FLOOR SHALL CORRESPOND WITH EACH
 OTHER. SOME OF THE DOORS ON THE FLOOR
 PLAN DON'T HAVE ANY NUMBER. ON THE
 SECOND FLOOR BETWEEN THE CONFERENCE
 ROOOM AND THE TWO OFFICES, THERE ARE TWO
 POCKET DOORS WHICH ARE NOT NUMBERED OR
 INDICATED ON THE DOOR SHCEDULE.THESE
 DOORS SHALL BE NOTED ON THE PLANS AND
 DOOR SCHEDULE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  