Plan Review Notes For Permit 06030097
Permit Number 06030097
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-25 00:00:00DENIED;
 1.PAGE P-0 WATER HEATER DETAIL. THERMAL
 EXPANSION TANK TO BE INSTALLED ON COLD
 WATER SIDE PER MANUFACTURE'S
 SPECIFICATIONS.
 2.PLUMBING NOTES NUMBER 16 FIRE STOP
 MATERIAL, LIST MANUFACTURE AND LIST THE
 UL NUMBERS.
 3.BAR AREA FLOOR SINKS REQUIRED FOR
 INDIRECT WASTE FROM ICE BINS,SODA AND
 BEER DISPENSOR DRAINS.
 4.WATER HAMMER ARRESTORS TO BE INSTALLED
 AS CLOSE TO SOURCE OF HAMMER AS POSSIBLE
 PER MANUFACTURE'S INSTALLATION
 INSTRUCTIONS.
 5.PAGE A.0 (PROJECT INFORMATION) 1526
 SQ. FT. GROUP DOES NOT MEET ALL OF THE
 EXCEPTIONS IN SECTION 403.2 (2) 15
 PEOPLE OR LESS.
 6.THE BAR AREA ON FIRST FLOOR SHOULD BE
 A-2 IN TABLE 403.1 NOT GROUP B. SHOW
 SEATING IN BAR AREA.
 7.ADA BATHROOM ON SECOND FLOOR, SHOWER
 IS REQUIRED TO MEET HANDICAP CODE
 SECTIONS 11-4.21.1 THRU 11-4.21.6 (SHOW
 DETAIL ON PLANS)
 8.LOUNGE SINK TO BE HANDICAP ACCESSIBLE.
 MUST COMPLY WITH CHAPTER 11 SECTIONS
 11-4.24.1 THRU 11-4.24.7. SHOW FRONTAL
 APPROACH ON PLANS AND A DETAIL OF
 CABINETS ON PLANS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695