| Plan Review Notes For Permit 06030097 |
| Permit Number |
06030097 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-11 00:00:00 | PLAN DENIED | | | 1) PLEASE REFER TO SECTION 13-101.1.3 | | | RENOVATIONS OF COMMERCIAL BUILDINGS | | | FLORIDA ENERGY CODE 2004. | | | 2) PLEASE REFER TO SECTION 602.2.1 2004 | | | FBC(M) MECHANICAL COLSIT DOORS MUST | | | MEET FIRE AND SMOKE INDEX OF 25-50. | | | 3) PLESAE SHOW FANSHUT DOWN ON | | | AIRHANDLER # 3 ON THE PLANS. | | | 4) PLEASE REFER TO SECTION 307.2.3 2004 | | | FBC(M) AUXILIARY AND SECONDARY DRAIN | | | SYSTEM FOR AIRHANHLERS 1,2,3,4 | | | 5) PLEASE PROVIDE DUCT SIZE ON THE PLANS | | | FOR AIRHANDLER #6. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|