| Plan Review Notes For Permit 06030097 |
| Permit Number |
06030097 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-25 00:00:00 | ******DENIED****** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. SHT A.4. | | | | | | 2) DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 3) DOES THE UPPER LEVEL MEET THE | | | REQUIREMENTS OF NFPA 101, SECTION | | | 8.6.9.2 IN REGARDS TO MEZZANINE AREA | | | LIMITATIONS? | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 5) A SMOKE DETECTOR IS REQUIRED IN THE | | | AREA OF THE FIRE ALARM CONTROL PANEL. | | | | | | 6) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR HANDRAILS AND GUARDS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|