| Date |
Text |
| 2006-03-29 00:00:00 | IN ELEC FOR REVIEW |
| | ******* UNSAT ******** |
| | |
| | 1) NOTE: PLEASE SEE ADDRESSING ON TITLE |
| | BLOCK FOR ENGINEERING FIRM SHALL |
| | CORRELATE WITH THE STATE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. ( |
| | DBPR). |
| | PLEASE SEE ADDRESS ON SITE LIST BUSINESS |
| | IN WELLINGTON. |
| | PLEASE ADJUST. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENTS IS |
| | MADE BY OTHER TRADES. |
| | FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SPECIFY THE FOLLOWING |
| | CURRENT CODES IN EFFECT. |
| | NFPA-70 2002 |
| | NFPA-101 2003 |
| | NFPA-72, 2002. |
| | PLEASE ADJUST ANY CODES REFERENCED ON |
| | PLANS AS NEEDED. |
| | |
| | 3) NOTE: PLEASE KNOW, WE ARE CURRENTLY |
| | UNDER THE 2004 FBC. |
| | PLEASE SEE CHAPTER 13, FOR ALL NEW |
| | REQUIREMENTS FOR COMMERICAL BUILDINGS |
| | AND THE ENERGY CODE. |
| | PLEASE PROVIDE A WORST CASE SCENERIO FOR |
| | VOLTAGE DROP. 13-413.1ABC.1.2 |
| | PLEASE PROVIDE AUTOMATED LIGHTING |
| | CONTROL SYSTEM AS REQUIRED PER |
| | 13-415.1.ABC.1.1 |
| | PLEASE PROVIDE COMPLETE SCHEDULING WITH |
| | THAT SYSTEM AND TIME OF USE AND MAX TIME |
| | ALLOWED. |
| | PLEASE PROVIDE THE ACCESSIBLE LOCATIONS |
| | FOR OVERIDES. |
| | PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE |
| | CONTROL FOR AREAS WITH PARTITION WALLS. |
| | PLEASE KNOW, THESE DEVICES SHALL BE |
| | CAPABLE OF OVER-RIDING THE LIGHTING |
| | CONTROL SYSTEM, WITH EXCEPTIONS ALLOWED |
| | FOR TIMES, OCCUPANCY ETC. |
| | PLEASE SEE 13-415.1.ABC.3 FOR TANDEM |
| | WIRING. |
| | PLEASE SUBMIT SPECS/MANUFACTURES SUT |
| | SHEETS FOR PROPOSED SYSTEM. |
| | |
| | 4) NOTE: PLEASE SEE SERVICE AS SHOWN ON |
| | RISER WILL NOT BE PERMITTED. |
| | PLEASE PROVIDE INFORMATION ON ANY |
| | EXISTING SERVICE, MAINS ETC. |
| | IF OLD SERVICE IS BEING REMOVED, PLEASE |
| | INDICATE. 215.5 |
| | PLEASE SEE MAINS ARE NOT GROUPED AS |
| | REQUIRED PER 230.72 |
| | PLEASE SEE THE NEW "FUTURE" TENANT MAIN |
| | AND METER WILL NOT BE PERMITTED AS SPACE |
| | DOES NOT ALLOW FOR ANY FUTURE TENANT |
| | SEPARATION AT THIS TIME. ANY FUTURE |
| | SERVICE, MAINS ETC WILL BE REVIEWED AT |
| | THAT TIME BASED ON PLANS, FIRE |
| | SEPARATIONS, OCCUPANCY ETC. |
| | 215.5, 230.2 |
| | |
| | 5) NOTE: PLEASE SEE MIN GUTTER |
| | CALCULATIONS SHALL BE PROVIDED AS GUTTER |
| | SIZE SHOWN FOR SEC'S AND TAPS DO NOT |
| | APPEAR TO MEET MININUM SIZE PER |
| | 366.6,314.40 FOR MIN TURNING RADIUS )IF |
| | APPLICABLE). |
| | |
| | 6) NOTE: PLEASE SEE 250.66 FOR MINUNUM |
| | SIZING OF THE GROUNDING ELECTRODE |
| | CONDUCTOR. |
| | (2/0) |
| | |
| | 7) NOTE: PLEASE SEE 2002 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLING UNITS. |
| | |
| | 8) NOTE: PLEASE SEE COMMENTS WITH |
| | RESPECT TO SEPARATION FROM A |
| | MERCHANTILE/(BAR) AND BUS OCCUPANCY. |
| | THIS IS NOT AN ELECTRICAL COMMENT, |
| | HOWEVER MAY AFFECT ELECTRICAL PLANS. |
| | |
| | 9) NOTE: PLEASE SEE MISSING SIGN CIRCUIT |
| | PER 600.5 |
| | |
| | 10) NOTE: PLEASE SEE MISSING RECEPTS |
| | ABOVE WINDOWS WHICH WILL BE REQUIRED PER |
| | 210.62. THIS IS TO ALLEAVIATE ANY |
| | EXTENSION CORDS LIKELY TO CAUSE PHYSICAL |
| | INJURY, RECEPTACLES MUST BE INSTALLED |
| | DIRECTLY ABOVEWINDOW, AND ONE |
| | RECEPTACLE IS REQUIRED FOR EVERY 12 |
| | LINEAR FT OR "MAJOR FRACTION THEREOF" (6 |
| | FT OR MORE) |
| | |
| | 11) NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EMERGENCY AND EXIT LTS. |
| | PLEASE SEE THE BRANCH CIRCUIT FEEDING |
| | THE UNIT EQUIPMENT SHALL BE THE SAME |
| | BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | PLEASE ADJUST CIRCUITING AS NEEDED. |
| | |
| | 12) NOTE: PLEASE PROVIDE MIN |
| | PHOTO-METRICS FOR EGRESS STAIRWAYS. |
| | PLEASE ALSO SEE MAIN AREA WHICH MAY ALSO |
| | REQUIRE ADDITIONAL FIXTURES AT FRONT |
| | AREA TO PROVIDE MIN LIGHTING LEVELS |
| | UNDER EMERGENCY CONDITIONS. |
| | THIS SHOULD BE DETAILED IN |
| | PHOTO-METRICS. |
| | PLEASE SEE 2003 LS 101 WHICH REQUIRES |
| | A MININUM OF 10FT CANDLES(108 LUX) UNDER |
| | NORMAL CONDITIONS AND 1FT CANDLE UNDER |
| | EMERGENCY CONDITIONS. PLEASE SEE STAIRS |
| | DO NOT APPEAR TO SHOW ANY EM BATTERY |
| | BACK UP FIXTURES AT THIS TIME? |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR |
| | ANY MISSING LOCATIONS WHICH MAY BE |
| | REQUIRED AND WILL AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | 13) NOTE: PLEASE SEE PHASE "B" OF WATER |
| | HEATER ON PANEL SCHEDULE. THIS SEEMS TO |
| | BE A MISPRINT. (2, 9) |
| | PLEASE ADJUST. |
| | 215.5 |
| | |
| | 14) NOTE: PLEASE ADJUST ANY LOADS FOR |
| | ADDED DEDICATED CIRCUITS FOR WINDOW |
| | RECEPTS, 220.12B, SIGN CIRCUIT 600.5 ARE |
| | TO BE FIGURED INTO LOAD CALCS. |
| | ETC. |
| | |
| | 15) NOTE: PLEASE SEE DISCONNECTING MEANS |
| | FOR AHU'S IN CLOSETS ON LOWER LEVEL DO |
| | NOT SEEM TO MEET 110.26 |
| | PLEASE ALSO SEE ACCESS TO DISC'S ON SOME |
| | UNITS ON UPPER LEVEL ALSO. |
| | |
| | 16) NOTE: PLEASE SEE GROUDING ELECTRODE |
| | SYSTEM INDICATES GEC TO THE "FOOTER |
| | STEEL" ?? PLEASE KNOW, THIS SEEMS TO BE |
| | AN EXISTING BLDG AND THE GEC IS NOT |
| | REQUIRED TO BE ATTACHED TO THE FOOTER |
| | STEEL AS THIS PROCESS MAY AFFECT THE |
| | STRUCTURAL INTEGRITY OF THE EXISTING |
| | FOOTER. |
| | THIS MAY BE DONE, HOWEVER THIS IS NOT |
| | REQUIRED. IF SHOWN ON RISER, THEN THIS |
| | WILL BE REQUIRED. |
| | ** THIS IS ONLY A NOTE AND NO CORRECTION |
| | IS NEED. INFORMATIONAL ONLY. |
| | |
| | 17) NOTE: PLEASE SHOW DISCONNECTING |
| | MEANS REQUIRED FOR WATER HEATER. |
| | 422.31 |
| | |
| | 18) NOTE: PLEASE REVISE ENERGY |
| | CALCULATIONS AND FORMS PER COMMENTS |
| | ABOVE. 13-415.1.ABC.1 |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS . |
| | |
| | ** WHEN RE-SUBMITTING PLANS AFTER ALL |
| | REVIEWS ARE COMPLETED. PLEASE BES URE TO |
| | COMPLETELY REVMOVED ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. ONE SET OF THE REMOVED |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED IN |
| | A SEPARATE SET FOR REFERENCE.. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |