2006-03-29 00:00:00IN ELEC FOR REVIEW
 ******* UNSAT ********
  
 1) NOTE: PLEASE SEE ADDRESSING ON TITLE
 BLOCK FOR ENGINEERING FIRM SHALL
 CORRELATE WITH THE STATE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION. (
 DBPR).
 PLEASE SEE ADDRESS ON SITE LIST BUSINESS
 IN WELLINGTON.
 PLEASE ADJUST.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENTS IS
 MADE BY OTHER TRADES.
 FAC 61G15-23.002
  
 2) NOTE: PLEASE SPECIFY THE FOLLOWING
 CURRENT CODES IN EFFECT.
 NFPA-70 2002
 NFPA-101 2003
 NFPA-72, 2002.
 PLEASE ADJUST ANY CODES REFERENCED ON
 PLANS AS NEEDED.
  
 3) NOTE: PLEASE KNOW, WE ARE CURRENTLY
 UNDER THE 2004 FBC.
 PLEASE SEE CHAPTER 13, FOR ALL NEW
 REQUIREMENTS FOR COMMERICAL BUILDINGS
 AND THE ENERGY CODE.
 PLEASE PROVIDE A WORST CASE SCENERIO FOR
 VOLTAGE DROP. 13-413.1ABC.1.2
 PLEASE PROVIDE AUTOMATED LIGHTING
 CONTROL SYSTEM AS REQUIRED PER
 13-415.1.ABC.1.1
 PLEASE PROVIDE COMPLETE SCHEDULING WITH
 THAT SYSTEM AND TIME OF USE AND MAX TIME
 ALLOWED.
 PLEASE PROVIDE THE ACCESSIBLE LOCATIONS
 FOR OVERIDES.
 PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE
 CONTROL FOR AREAS WITH PARTITION WALLS.
 PLEASE KNOW, THESE DEVICES SHALL BE
 CAPABLE OF OVER-RIDING THE LIGHTING
 CONTROL SYSTEM, WITH EXCEPTIONS ALLOWED
 FOR TIMES, OCCUPANCY ETC.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM
 WIRING.
 PLEASE SUBMIT SPECS/MANUFACTURES SUT
 SHEETS FOR PROPOSED SYSTEM.
  
 4) NOTE: PLEASE SEE SERVICE AS SHOWN ON
 RISER WILL NOT BE PERMITTED.
 PLEASE PROVIDE INFORMATION ON ANY
 EXISTING SERVICE, MAINS ETC.
 IF OLD SERVICE IS BEING REMOVED, PLEASE
 INDICATE. 215.5
 PLEASE SEE MAINS ARE NOT GROUPED AS
 REQUIRED PER 230.72
 PLEASE SEE THE NEW "FUTURE" TENANT MAIN
 AND METER WILL NOT BE PERMITTED AS SPACE
 DOES NOT ALLOW FOR ANY FUTURE TENANT
 SEPARATION AT THIS TIME. ANY FUTURE
 SERVICE, MAINS ETC WILL BE REVIEWED AT
 THAT TIME BASED ON PLANS, FIRE
 SEPARATIONS, OCCUPANCY ETC.
 215.5, 230.2
  
 5) NOTE: PLEASE SEE MIN GUTTER
 CALCULATIONS SHALL BE PROVIDED AS GUTTER
 SIZE SHOWN FOR SEC'S AND TAPS DO NOT
 APPEAR TO MEET MININUM SIZE PER
 366.6,314.40 FOR MIN TURNING RADIUS )IF
 APPLICABLE).
  
 6) NOTE: PLEASE SEE 250.66 FOR MINUNUM
 SIZING OF THE GROUNDING ELECTRODE
 CONDUCTOR.
 (2/0)
  
 7) NOTE: PLEASE SEE 2002 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS.
  
 8) NOTE: PLEASE SEE COMMENTS WITH
 RESPECT TO SEPARATION FROM A
 MERCHANTILE/(BAR) AND BUS OCCUPANCY.
 THIS IS NOT AN ELECTRICAL COMMENT,
 HOWEVER MAY AFFECT ELECTRICAL PLANS.
  
 9) NOTE: PLEASE SEE MISSING SIGN CIRCUIT
 PER 600.5
  
 10) NOTE: PLEASE SEE MISSING RECEPTS
 ABOVE WINDOWS WHICH WILL BE REQUIRED PER
 210.62. THIS IS TO ALLEAVIATE ANY
 EXTENSION CORDS LIKELY TO CAUSE PHYSICAL
 INJURY, RECEPTACLES MUST BE INSTALLED
 DIRECTLY ABOVEWINDOW, AND ONE
 RECEPTACLE IS REQUIRED FOR EVERY 12
 LINEAR FT OR "MAJOR FRACTION THEREOF" (6
 FT OR MORE)
  
 11) NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EMERGENCY AND EXIT LTS.
 PLEASE SEE THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING AS NEEDED.
  
 12) NOTE: PLEASE PROVIDE MIN
 PHOTO-METRICS FOR EGRESS STAIRWAYS.
 PLEASE ALSO SEE MAIN AREA WHICH MAY ALSO
 REQUIRE ADDITIONAL FIXTURES AT FRONT
 AREA TO PROVIDE MIN LIGHTING LEVELS
 UNDER EMERGENCY CONDITIONS.
 THIS SHOULD BE DETAILED IN
 PHOTO-METRICS.
 PLEASE SEE 2003 LS 101 WHICH REQUIRES
 A MININUM OF 10FT CANDLES(108 LUX) UNDER
 NORMAL CONDITIONS AND 1FT CANDLE UNDER
 EMERGENCY CONDITIONS. PLEASE SEE STAIRS
 DO NOT APPEAR TO SHOW ANY EM BATTERY
 BACK UP FIXTURES AT THIS TIME?
 PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR
 ANY MISSING LOCATIONS WHICH MAY BE
 REQUIRED AND WILL AFFECT ELECTRICAL
 PLANS.
  
 13) NOTE: PLEASE SEE PHASE "B" OF WATER
 HEATER ON PANEL SCHEDULE. THIS SEEMS TO
 BE A MISPRINT. (2, 9)
 PLEASE ADJUST.
 215.5
  
 14) NOTE: PLEASE ADJUST ANY LOADS FOR
 ADDED DEDICATED CIRCUITS FOR WINDOW
 RECEPTS, 220.12B, SIGN CIRCUIT 600.5 ARE
 TO BE FIGURED INTO LOAD CALCS.
 ETC.
  
 15) NOTE: PLEASE SEE DISCONNECTING MEANS
 FOR AHU'S IN CLOSETS ON LOWER LEVEL DO
 NOT SEEM TO MEET 110.26
 PLEASE ALSO SEE ACCESS TO DISC'S ON SOME
 UNITS ON UPPER LEVEL ALSO.
  
 16) NOTE: PLEASE SEE GROUDING ELECTRODE
 SYSTEM INDICATES GEC TO THE "FOOTER
 STEEL" ?? PLEASE KNOW, THIS SEEMS TO BE
 AN EXISTING BLDG AND THE GEC IS NOT
 REQUIRED TO BE ATTACHED TO THE FOOTER
 STEEL AS THIS PROCESS MAY AFFECT THE
 STRUCTURAL INTEGRITY OF THE EXISTING
 FOOTER.
 THIS MAY BE DONE, HOWEVER THIS IS NOT
 REQUIRED. IF SHOWN ON RISER, THEN THIS
 WILL BE REQUIRED.
 ** THIS IS ONLY A NOTE AND NO CORRECTION
 IS NEED. INFORMATIONAL ONLY.
  
 17) NOTE: PLEASE SHOW DISCONNECTING
 MEANS REQUIRED FOR WATER HEATER.
 422.31
  
 18) NOTE: PLEASE REVISE ENERGY
 CALCULATIONS AND FORMS PER COMMENTS
 ABOVE. 13-415.1.ABC.1
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS .
  
 ** WHEN RE-SUBMITTING PLANS AFTER ALL
 REVIEWS ARE COMPLETED. PLEASE BES URE TO
 COMPLETELY REVMOVED ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. ONE SET OF THE REMOVED
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED IN
 A SEPARATE SET FOR REFERENCE..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]