| Date |
Text |
| 2006-04-19 00:00:00 | 1) SUBMIT DRAWINGS SHOWING THE PREVIOUS |
| | LAYOUT OF THE BUILDING. SEE FBC.106.3.5 |
| | |
| | 2) FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 3)THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMMENDMENT TO FBC 106.3.3 |
| | FOR INFORMATION PLEASE SEE THE STATE |
| | WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE |
| | REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. |
| | ALL STATE WIDE PRODUCT APPROVAL NEEDS |
| | THE STATE COVER SHEETS. PRODUCT |
| | APPROVALS ARE REQUIRED FOR DOORS/GLASS |
| | BLOCK/WINDOWS ETC. |
| | |
| | 4)EXISTING BUILDING CODE. 501.2 |
| | CONFORMANCE. |
| | AN EXISTING BUILDING OR PORTION THEREOF |
| | SHALL NOT BE ALTERED SUCH THAT THE |
| | BUILDING BECOMES LESS SAFE OR ENERGY |
| | EFFICIENT THAN ITS EXISTING CONDITION. |
| | IF IN THE ALTERATION THE CURRENT LEVEL |
| | OF SAFETY OR SANITATION IS TO BE |
| | REDUCED, THE PORTION ALTERED SHALL |
| | CONFORM TO THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. SEE |
| | DEMO NOTES 'B' DOOR #114. |
| | |
| | 5)11-4.11 PLATFORM LIFTS (WHEELCHAIR |
| | LIFTS). 11-4.11.1 LOCATION. |
| | PLATFORM LIFTS (WHEELCHAIR LIFTS) |
| | PERMITTED BY SECTION 11-4.1 SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION |
| | 11-4.11. |
| | 11-4.11.2 OTHER REQUIREMENTS. |
| | IF PLATFORM LIFTS (WHEELCHAIR LIFTS) ARE |
| | USED, THEY SHALL COMPLY WITH SECTIONS |
| | 11-4.2.4 , 11-4.5 , 11-4.27 , AND ASME |
| | A17.1, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS , SECTION XX, 1990. 11-4.11.3 |
| | ENTRANCE. IF PLATFORM LIFTS ARE USED |
| | THEN THEY SHALL FACILITATE UNASSISTED |
| | ENTRY, |
| | OPERATION, AND EXIT FROM THE LIFT IN |
| | COMPLIANCE WITH SECTION 11-4.11.2 . |
| | |
| | 6) 1607.7.1 HANDRAILS AND GUARDS . |
| | HANDRAIL ASSEMBLIES AND GUARDS SHALL BE |
| | DESIGNED TO RESIST A LOAD OF 50 PLF |
| | (0.73 KN/M) APPLIED IN ANY DIRECTION AT |
| | THE TOP AND TO TRANSFER THIS LOAD |
| | THROUGH THE SUPPORTS TO THE STRUCTURE. |
| | SUBMIT THE INFORMATION FOR THE GLASS AT |
| | THE RAILING. |
| | |
| | 7) INDICATE THE CLEAR FLOOR SPACE FOR |
| | THE WATER CLOSET. SEE 11-4.16.2. |
| | CLEAR FLOOR SPACE FOR THE LAVATORY IS |
| | REQUIRED AND ALL OTHER DETAILS. SEE |
| | 11-4.19.3 FOR MORE INFORMATION. |
| | |
| | 8) SINKS REQUIRED TO BE ACCESSIBLE BY |
| | SECTION 11-4.1 SHALL COMPLY WITH SECTION |
| | 11-4.24 . |
| | |
| | 9)704.8 ALLOWABLE AREA OF OPENINGS. |
| | THE MAXIMUM AREA OF UNPROTECTED OR |
| | PROTECTED OPENINGS PERMITTED IN AN |
| | EXTERIOR WALL IN ANY STORY SHALL NOT |
| | EXCEED THE VALUES SET FORTH IN TABLE |
| | 704.8 . WHERE BOTH UNPROTECTED AND |
| | PROTECTED OPENINGS ARE LOCATED IN THE |
| | EXTERIOR WALL IN ANY STORY, THE TOTAL |
| | AREA OF THE OPENINGS SHALL COMPLY WITH |
| | THE FOLLOWING FORMULA: |
| | |
| | 10) THE DIMENTION FOR THE WIDTH OF |
| | STAIRS ON THE FIRST FLOOR AND THE SECOND |
| | FLOOR DONOT MATCH. PLEASE CLARIFY. |
| | |
| | 11) FIRE SUPRESSION SYSTEM DRAWINGS IS |
| | REQUIRED FOR REVIEW BEFORE PERMIT CAN BE |
| | ISSUED. |
| | |
| | 12) INDICATE THE CORRECT FLOOD ZONE ON |
| | THE DRAWINGS. THE IS NO "X" ZONES IN THE |
| | CITY OF WEST PALM. |
| | |
| | 13) INFO. ONLY: THE AREA REFERED TO AS A |
| | MEZZANIE EXCEEDS THE ONE-THIRD |
| | REQUIREMENT OF THE TOTAL FLOOR AREA. |
| | THEREFORE, THE AREA WILL BE CONSIDER AS |
| | A SECOND FLOOR. THE TYPE OF CONSTRUCTION |
| | INDICATED ON THE DRAWINGS IS TYPE IIA |
| | SPRINKLED. THE FLOOR OF A TYPE IIA |
| | BUILDING REQUIRES A ONE-HOUR RATING.SEE |
| | FBC.TABLE 601. HOWEVER, BUSINESS LESS |
| | THAN TWO STORY WITH 9000SF CAN BE TYPE |
| | VB CONSTRUCTION WHICH IS THE MINIMUM |
| | CONSTRUCTION TYPE. TYPE VB CONSTRUCTION |
| | HAS A 'O' FLOOR RATING. WITH A TYPE IIA |
| | CONSTRUCTION THE STAIRWAYS SHALL BE |
| | ENCLOSE WITH A ONE-HOUR RATED WALL. |
| | |
| | 14) WHAT TYPE OF BAR WILL BE WILL BE |
| | INSTALL AT THIS BUSINESS. ALSO INDICATE |
| | THE TYPE OF SERVICES THE OFFICES WILL |
| | PROVIDE. WILL THERE BE SEATING AT THE |
| | BAR AREA? PLEASE SHOW ALL THIS |
| | INFORMATION ON THE DRAWINGS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | FAX:(561)805-67312 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |