2006-10-05 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD MUST MAKE
 CHANGES/REVISIONS TO HIS/HER DESIGN. SEE
 CHAPTER 471 FLORIDA STATUTES.
  
 2} WHEN MAKING REVISIONS, USE THE SAME
 PAGE NUMBER AS THE SHEET ORIGINALLY
 PERMITED, FOR CHANGES AFFECTING THAT
 SHEET.
  
 3} REVISE SHEETS WITH THE SAME SIZE
 SHEETS AS ORIGINALLY PERMITTED FOR THE
 SAKE OF CONSISTENCY IN RECORD RETENTION
 AND GOOD DRAFTING PRACTICE. 106.1.3 FBC
 AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  