Plan Review Notes
Plan Review Notes For Permit 06030093
Permit Number 06030093
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE NOTE NOW APPEARING ON THE RISER
 REGARDING CONDUIT TO THE "MAIN BUILDING"
 INDICATES THAT THE SERVICE IS ON A
 SEPARATE STRUCTURE FROM THE MAIN HOUSE.
 PLEASE SHOW THE LOCATION OF ALL SERVICE
 EQUIPMENT SO THAT COMPLIANCE WITH
 ARTICLES 225, 250, AND 230 CAN BE
 REVIEWED. INDICATE CORRECT DISCONNECTING
 MEANS, GROUNDING AND GROUPING OF MAINS
 AND DISCONNECTING MEANS.
  
 2} THE #1 FEEDERS TO THE 150 AMP
 SUB-PANEL HAVE A 200 AMP OVERCURRENT
 PROTECTION, AND MUST BE INCREASED TO A
 MINIMUM OF 2/0CU PER 310.15.
  
 3} INDICATE THE ACTUAL SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR FOR THE
 SERVICE , NOT THE NUMBER OF THE ARTICLE
 REQUIRING IT.
  
 4} A SMOKE DETECTOR IS REQUIRED ON THE
 FIRST LEVEL AT THE STAIRS PER R313
 .1.1 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  