| Plan Review Notes For Permit 06030093 |
| Permit Number |
06030093 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-04 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE NOTE NOW APPEARING ON THE RISER | | | REGARDING CONDUIT TO THE "MAIN BUILDING" | | | INDICATES THAT THE SERVICE IS ON A | | | SEPARATE STRUCTURE FROM THE MAIN HOUSE. | | | PLEASE SHOW THE LOCATION OF ALL SERVICE | | | EQUIPMENT SO THAT COMPLIANCE WITH | | | ARTICLES 225, 250, AND 230 CAN BE | | | REVIEWED. INDICATE CORRECT DISCONNECTING | | | MEANS, GROUNDING AND GROUPING OF MAINS | | | AND DISCONNECTING MEANS. | | | | | | 2} THE #1 FEEDERS TO THE 150 AMP | | | SUB-PANEL HAVE A 200 AMP OVERCURRENT | | | PROTECTION, AND MUST BE INCREASED TO A | | | MINIMUM OF 2/0CU PER 310.15. | | | | | | 3} INDICATE THE ACTUAL SIZE OF THE | | | GROUNDING ELECTRODE CONDUCTOR FOR THE | | | SERVICE , NOT THE NUMBER OF THE ARTICLE | | | REQUIRING IT. | | | | | | 4} A SMOKE DETECTOR IS REQUIRED ON THE | | | FIRST LEVEL AT THE STAIRS PER R313 | | | .1.1 FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|