 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE AIC RATINGS FOR THE SERVICE
 EQUIPMENT PER 110.9 AND 110.10.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE FOR
 THE NEW PANEL SO THAT BRANCH CIRCUIT
 COMPLIANCE MAY BE REVIEWED.
  
 3} THE 1/0 CU ON THE RISER IS INCORRECT.
 TO THE PANEL 2/0 MINIMUM IS REQUIRED PER
 310.15(B).
  
 4} THE NOTE REGARDING GROUNDING
 (250.83C) SHOULD READ 250.50, THE
 CURRENT 2002 CODE SECTION.
  
 5} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST BE SPACED PER 210.52(C).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  