| Plan Review Notes For Permit 06030093 |
| Permit Number |
06030093 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-14 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE AIC RATINGS FOR THE SERVICE | | | EQUIPMENT PER 110.9 AND 110.10. | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE FOR | | | THE NEW PANEL SO THAT BRANCH CIRCUIT | | | COMPLIANCE MAY BE REVIEWED. | | | | | | 3} THE 1/0 CU ON THE RISER IS INCORRECT. | | | TO THE PANEL 2/0 MINIMUM IS REQUIRED PER | | | 310.15(B). | | | | | | 4} THE NOTE REGARDING GROUNDING | | | (250.83C) SHOULD READ 250.50, THE | | | CURRENT 2002 CODE SECTION. | | | | | | 5} THE KITCHEN COUNTERTOP RECEPTACLES | | | MUST BE SPACED PER 210.52(C). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | | | |
|