| 2006-03-13 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS.(NOTE:HOW LONG IS THE RISER AND | | | THE DROP) | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES.(NOTE:WHAT | | | TYPE MATERIAL IS THE DROP FROM METER AND | | | RISER TO POOL HEATER? ALSO PER TABLE | | | 402.4(2) RISER TO POOL HEATER SHALL BE | | | ONE INCH, 1" BECAUSE OF 400 CF, PLEASE | | | CORRECT) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 |
|