2006-03-13 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.(NOTE:HOW LONG IS THE RISER AND
 THE DROP)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.(NOTE:WHAT
 TYPE MATERIAL IS THE DROP FROM METER AND
 RISER TO POOL HEATER? ALSO PER TABLE
 402.4(2) RISER TO POOL HEATER SHALL BE
 ONE INCH, 1" BECAUSE OF 400 CF, PLEASE
 CORRECT)
  
 END OF COMMENTS:
  