| 2007-03-11 11:40:24 | *** REDLINED PLANS/PROVISO/ REVISON NEEDED BEFORE | | | ROUGH*** | | | | | | | | | 1) NOTE: PLEASE SEE NFPA-72 11.8.3 AS THE SA IN MASTER | | | BEDROOOM MUST BE INSTALLED WITHIN 3FT OF THE HIGHEST | | | POINT ON A SLOPED CEILING AND MUST BE INSTALLTED WITHIN | | | 12INCHES ON THE HIGHEST POINT ON A FLAT/TRAY CEILING. | | | THIS DEVICE DOES NOT SEEMS LIKE IT WILL MEET THIS | | | SECTION AND SHALL BE FEILD VERIFIED AS ELEVATION OF | | | CEILING IS NOT ON ELECTRICAL PLANS. | | | | | | 2) NOTE: PLEASE SEE THE PANEL SCHEDULES BOTH INDICATE | | | 4/0 CONDUCTORS FOR THE FEEDERS TO EACH OF THE PANELS, | | | YET THE RISER DIAGRAM SHOWS 2/0'S FOR EACH OF THESE.? | | | PLEASE CORRELATE. THIS WAS SHOWN THIS WAY ON THE | | | PREVIOUS SUBMITTED REVISIONS, HOWEVER WAS MISSED. | | | | | | ** PLEASE REVISE THE ABOVE WITH ANY OTHER REVSIONS | | | BEFORE ROUGH ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | 561-805-6717 | | | [email protected] |
|