Plan Review Notes
Plan Review Notes For Permit 06030075
Permit Number 06030075
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-20 14:10:43** MECHANICAL REVISION **
 FOR VOIDED BUILDING PERMIT #05070398
 *** DENIED ***
 1) SEE YELLOW HIGH-LIGHT ON MECHANICAL PLANS SHOWING
 DUCTS THAT NEED TO BE SIZED.
  
 2) AFTER SIZING THE SUPPLY AIR DUCT TO THE MASTER SUITE
 CHECK TO MAKE SURE THE RETURN AIR DUCT TO THE MASTER
 SUITE IS LARGE ENOUGH,SEE 2004 FBC/R M1602.4 (C)
 EXCEPT.
  
 ** 2004 FBC/R M1602.4BALANCED RETURN AIR.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.