Plan Review Notes
Plan Review Notes For Permit 06030075
Permit Number 06030075
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-18 14:45:56*** UNSAT ***
  
 ** ORIGINAL REVIEW DONE UNDER 05070398, THIS RE-STAMP
 WAS NOT REVIEWED UNDER THIS PERMIT NUMBER.
  
 1) NOTE: PLEASE INDICATE ALL REVISIONS IN TITLE BLOCKS
 AND INDICATE BY CLOUDS/TRIANGLES ON PLANS.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THE RISER NOW IS COMPLETELY REVISED
 WHICH NOW INDICATES THE SUB PANEL BEING REMOVED HOWEVER
 THE PLANS STILL INDICATE MANY ELECTRICAL ITEMS NOT
 LISTED ON ANY PANEL SCHEDULE. PLEASE ALSO SEE THE LOAD
 CALCULATIONS ALSO STILL LIST MANY ELECTRICAL ITEMS NOT
 ON ANY PANEL SCHEDULE??
 PANEL *C* WAS REMOVED.
 PLEASE CORRELATE AND REVISE ACCORDINGLY.
 215.5, 310.16, 240.4, 408.4
 FBC 106.1.2
  
 3) NOTE: PLEASE REVISE PANEL SCHEDULES FOR ALL ROOMS
 AND AREAS WHICH ARE REQUIRED TO SPECIFIC. PLEASE SEE
 408.4 WHICH THE COMMENTARY OF THIS SECTION STATES;
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 4) NOTE: PLEASE VERIFY THE MODEL NUMBER FOR PANEL *B*
 WHICH SHOWS THIS AS A 125AMP PANEL WHEN THIS IS A 200A
 PANEL.
 215.5.
 FBC 106.1.2 PLEASE COORDINATE.
  
 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON PLANS FOR DESIGN.
 2002 NFPA-70, 2002 NFPA-72
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]