Plan Review Notes
Plan Review Notes For Permit 06030036
Permit Number 06030036
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-03 00:00:00 
 PROVIDE A SITE PLAN, FLOOR PLAN OR BOTH
 TO INDICATE THE LOCATION OF ALL SERVICE
 AND GENERATOR EQUIPMENT.
  
 A PARTIAL RISER DIAGRAM WAS SUBMITTED
 SHOWING A 200AMP PANEL AND A 100 AMP
 TRANSFER SWITCH. A PICTURE WAS SUBMITTED
 SHOWING 2 PANELS SIDE BY SIDE APPARANTLY
 IN THE RESIDENCE.
  
 ANOTHER RISER(WITH NO NAME OR SIGNATURE
 ON IT)SHOWS A MAINAN EXISTING PANEL,
 AND A 100 AMP TRANSFER SWITCH, AND A
 RACE WAY GOING TO A GENERATOR "POWER
 INLET".PROVIDE A CALCULATION FOR THE
 LOAD TO BE SERVED BY THE GENERATOR . SEE
 702.5. HEAT, IF IN THE CALCULATION, MUST
 BE AT 100%.
  
 PLEASE SUBMIT TWO COPIES OF EVERYTHING,
 AND INCLUDE THE APPLICATION NOT FOUND
 WITH THIS RESUBMITTAL PACKAGE. TAKE OUT
 ALL DOCUMENTS THAT HAVE BEEN CHANGED OR
 ARE NOT NEEDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  