| Plan Review Notes For Permit 06030036 |
| Permit Number |
06030036 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-03 00:00:00 | | | | PROVIDE A SITE PLAN, FLOOR PLAN OR BOTH | | | TO INDICATE THE LOCATION OF ALL SERVICE | | | AND GENERATOR EQUIPMENT. | | | | | | A PARTIAL RISER DIAGRAM WAS SUBMITTED | | | SHOWING A 200AMP PANEL AND A 100 AMP | | | TRANSFER SWITCH. A PICTURE WAS SUBMITTED | | | SHOWING 2 PANELS SIDE BY SIDE APPARANTLY | | | IN THE RESIDENCE. | | | | | | ANOTHER RISER(WITH NO NAME OR SIGNATURE | | | ON IT)SHOWS A MAINAN EXISTING PANEL, | | | AND A 100 AMP TRANSFER SWITCH, AND A | | | RACE WAY GOING TO A GENERATOR "POWER | | | INLET".PROVIDE A CALCULATION FOR THE | | | LOAD TO BE SERVED BY THE GENERATOR . SEE | | | 702.5. HEAT, IF IN THE CALCULATION, MUST | | | BE AT 100%. | | | | | | PLEASE SUBMIT TWO COPIES OF EVERYTHING, | | | AND INCLUDE THE APPLICATION NOT FOUND | | | WITH THIS RESUBMITTAL PACKAGE. TAKE OUT | | | ALL DOCUMENTS THAT HAVE BEEN CHANGED OR | | | ARE NOT NEEDED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|