| 2006-03-09 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ENGINEER MUST SIGN AND SEAL THE | | | PLANS PER 471 FS. | | | | | | 2} THE PANEL SHOWN ON THEW PLAN MUST | | | COMPLY WITH 110.26 CLEARANCE | | | REQUIREMENTS. | | | | | | 3} INDICATE THE PROPOSED LOCATIONS OF | | | ALL DEVICES TO BE ADDED SO THAT | | | COMPLIANCE WITH THE 2002 NEC CAN BE | | | REVIEWED FOR CORRECT CIRCUITING AND | | | SPACING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|