| Plan Review Notes For Permit 06030007 |
| Permit Number |
06030007 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-13 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33).(NOTE: THE BTU LOAD FOR THE | | | GENERATOR IS 1,020,000 NOT 600,000 | | | PLEASE CORRECT) | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | END OF COMMENTS: | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | | | | |
|