| Plan Review Notes For Permit 06021280 |
| Permit Number |
06021280 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-10-24 16:15:52 | REVISED ENERGY CALCULATIONS CHECKLIST. | | | | | | 1- ENERGY CALCULATIONS WERE SUBMITTED FOR RE-STAMPING | | | BECAUSE THE ONES FROM THE FIELD SET WERE LOST. | | | PROVIDED ENERGY CALCULATIONS DON'T MATCH APPROVED ONES. | | | THEREFORE, THIS IS A REVISION AND $70.00 REVISION FEES | | | ARE DUE(NEW ENERGY CALCULATIONS AND MANUAL J | | | CALCULATIONS PROVIDED). | | | | | | 2- PROVIDE 2 COPIES OF REVISED ENERGY CALCULATIONS. | | | | | | 3- NEW ENERGY CALCULATIONS CALL FOR R-30 FOR ADJACENT | | | WOOD FRAMED WALL (ITEM 9(B).REVISE PLANS AS REQUIRED | | | SHOWING HOWTHIS R-30 VALUEIS ACHIEVED ON A 2X4 STUD | | | WALL?.SEE SHEET A-8. | | | ***NOTE: IF USING BUTT INSULATION, THENONLY R-11 CAN | | | BE ACHIEVEDON A 2X4 WALL. | | | | | | 4- PROVIDE REVISED ENERGY CALCULATIONS FORM 600A-2004R. | | | | | | | | | 5- PROVIDE CORRECT CONTRACTOR'S NAMEAND COMPLETE ALL | | | INFORMATION ON TOP OF ENERGY CALCULATIONS FORM. | | | | | | 6- OWNER/AGENT TO DATE FORM OF FORM. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | |
|