Plan Review Notes
Plan Review Notes For Permit 06021280
Permit Number 06021280
Review Stop E
Sequence Number 3
Notes
Date Text
2008-01-31 07:52:00 
  
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE AS
 THEY CANNOT BE VERIFIED AS BEING MADE BY THE DESIGNER
 OF RECORD AS REQUIRED BY FS 471 OR 481, AS APPLICABLE.
 PLANS MUST BE REDRAWN BY THE DESIGNER OF RECORD, THEY
 MUST BE DATED TO REFLOECT THE REVISION DATE.
  
 2} REVISE THE LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 3} ADD THE NEW EQUIPMENT TO THE PANEL SCHEDULE PER
 106.3.5.4(8) FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.