| 2006-06-19 00:00:00 | *** DENIED *** | | | 1) DUCT SIZES ON MECHANICAL PLANS ARE | | | INCORRECT, PLEASE REVIEW MANUAL J | | | CALCULATIONS (UNDER CFM'S) AND CORRECT | | | DUCT SIZES. | | | | | | 2) HEATER KW ON MECHANICAL PLANS IS | | | INCORRECT, PLEASE SEE ENERGY | | | CALCULATIONS (HEATER SYSTEMS) AND | | | CORRECT HEATER KW ON PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|