2006-07-06 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2- HOUSE IS LOCATED IN FLOOD ZONE A5.
 DETERMINED FLOOD ELEVATION IS 7'-0".
 CITY OF W.P.B ORDINANCE SEC.94-546(B)(1)
 REQUIRES MIN. FLOOR ELEVATION TO BE AT
 LEAST 6" ABOVE THE DETERMINED FLOOD
 ELEVATION. GARAGE FIN. FLOOR ELEVATION
 SHOWN ON PLANS AND SURVEY IS 7'-0".
 REVISE PLANS AND SURVEY AS REQUIRED.
  
 3- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 FOR:
 A) SIDING. SEE PLANS. NO SUBMITTED WITH
 RE-SUBMITTAL PACKAGE.
 B) METAL ROOFING. NO SUBMITTED.
 C) SINGLE HUNG WINDOWS. PROVIDE DADE
 COUNTY NOA REPORT THAT MATCHES ONE
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL
 VISIT DCA SITE WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD SPECIFIC NOA SUBMITTED TO
 OBTAIN FLORIDA PRODUCT APPROVAL.
 ***NOTE: SEE APPROVED PACKAGE FOR FRENCH
 DOORS WITH SIDELITES PRODUCT APPROVAL.
 USE AS SAMPLE OF COMPLETE PRODUCT
 APPROVAL SUBMITTAL. PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND EXACT
 NOA REPORT THAT WAS APPROVED BY DCA.
 D) AWNING WINDOWS. NOT SUBMITTED.
 E) FIXED WINDOWS. PROVIDE EXACT DADE
 COUNTY NOA SUBMITTED FOR APPROVAL. SEE
 COMMENTS ABOVE.
 F) BAHAMA SHUTTERS. NOT SUBMITTED.
 G) PRECAST LINTELS. NOT SUBMITTED.
 H) ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS. SEE DETAIL SECTIONS
 AND TRUSS ANCHOR SCHEDULE. NOT SUBMITTED
 I) 4'X8' WITH SIDELITES ENTRY DOOR. NOT
 SUBMITTED WITH THIS PACKAGE.
 J) FRENCH DOORS. PROVIDE CURRENT NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 K) WINDOW MULLIONS: PROVIDE CURRENT
 NOAS. ONES SUBMITTED EXPIRED ON 6-28-06.
 L) GARAGE DOORS AS SHOWN ON PLANS. NOT
 SUBMITTED WITH THIS PACKAGE.
  
 4- REMAINDER. DESIGNER OF RECORD TO RE-
 REVIEW AND APPROVE ALL REVISED PRODUCT
 APPROVALS. SEC. 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 5- PROVIDE COMPLETE INFORMATION FOR R-19
 ICYNENE INSULATION TO VERIFY COMPLIANCE
 WITH THE PROPOSED INSTALLATION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 AND
 R806.4 2004 RESIDENTIAL CODE.
 INFORMATION WAS NOT SUBMITTED.
  
 6- REVISE ENERGY CALCULATIONS:
 A) REVISE NAME OF BUILDER.
 B) CEILING INSULATION R VALUE DOESN'T
 MATCH PLANS.
  
 7- ARCHITECT TO SPECIFY R-30 INSULATION
 ON ADJACENT WALL BY GARAGE AREA TO MATCH
 ENERGY CALCULATIONS.
  
 8- REVISE SURVEY. A) NEED TO RAISE
 GARAGE FINISH FLOOR ELEVATION. SEE ITEM
 #2 ABOVE.
 B) INCLUDE FRONT AND REAR PORCHES TO
 MATCH ARCHITECT'S PLANS.
  
 9- TRUSSES PACKAGE SUBMITTED NEED:
 A) 2 COMPLETE SETS.
 B) DESIGNER OF RECORD TO REVIEW AND
 APPROVE PACKAGE IN WRITTING.
 C) TRUSS ENGINEER TO SIGN, SEAL, DATE
 AND PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 AND SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 10- SHEET A-7: STAIR RATIO SHOWN EXCEEDS
 THE RATIO REQUIRED SEC. R311.5.3.2. TWO
 RISERS AT 6.7" AND ONE TREAD AT 12"
 EQUALS 25.4. REVISE AS REQUIRED.
  
 11- SHEET A-8: DETAIL 5/A9 AND
 INFORMATION SHOWN ON FOUNDATION PLAN IS
 CONFUSING. CLARIFY HOW IS THE COLUMN C-1
 AND 8"X20" WITH 6-#5 VERT. INSTALLED.
 PROVIDE CLEAR DETAIL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  