| Plan Review Notes For Permit 06021280 |
| Permit Number |
06021280 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-09 00:00:00 | DENIED; | | | 1.AUTOMATIC CLOTHES WASHER DRAIN | | | REQUIRED TO BE 3" SEE FBC-2004 PLUMBING | | | SEC. 406.3. CLEANOUT AT 48" AFF. | | | 2.SECOND FLOOR BATH CANNOT DISCHARGE | | | INTO THE VENT FOR THE AUTOMATIC CLOTHES | | | WASHER, MUST HAVE ON STACK. | | | 3.FLOOR PLAN SHOWS TWO TOILETS IN MASTER | | | BATHROOM SANITARY RISER DIAGRAMONLY | | | SHOWS ONE. | | | 4.FIRST FLOOR SHOWER BATH VENT REQUIRED | | | ON LAV TO VENT BATHROOM GROUP. | | | 5.PLEASE SUBMIT THE MANUFACTURE'S SPECS. | | | FOR THE ICE MACHINE. (FLOOR DRAIN MAY BE | | | REQUIRED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|