| 2006-03-09 00:00:00 | *** DENIED *** |
| | 1) MECHANICAL PLANS PAGE M-1 EQUIPMENT |
| | SCHEDULE IS SHOWING INCORRECT TOTAL AND |
| | SENSIBLE BTU'S, PLEASE CORRECT. |
| | |
| | 2) PLEASE SUBMITT A MANUAL J (LONG FORM) |
| | SHOWING CFM'S TO EACH ROOM. PLEASE NOTE |
| | THE TRAIN TRACE 700 IS NOT RECOGNIZED AS |
| | A REPLACEMENT. |
| | |
| | 3) ENERGY CALCULATIONS ARE SHOWING |
| | CONDITIONEDFLOOR AREA AS 2,949 SQ. |
| | FT., PLANS ARE SHOWING 3,286 A/C SQ. |
| | FT., PLEASE CORRECT. |
| | |
| | 4) OWNER/AGENT ALSO NEEDS TO SIGN |
| | CORRECTED ENERGY CAL'S. |
| | |
| | 5) TRANSFER RETURN AIR GRILL TO MASTER |
| | SUITE IS TO SMALL, SEE NOTE #6. |
| | |
| | 6)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 7) MAIN RETURN AIR GRILL TO AHU #2 |
| | (18X18) IS TO SMALL FOR A 5 TON SYSTEM. |
| | |
| | 8) PLEASE PROVIDE DETAILED MANUFACTURE'S |
| | SPECIFICATION'S AND INSTALLATION |
| | INSTRUCTIONS FOR THE GAS FIRE PLACE. |
| | |
| | 9) OPEN GRILL IN COVERED PORCH WILL NEED |
| | AN APPROVED EXHAUST HOOD, PER 2004 FBC/M |
| | 505.3 . |
| | |
| | 10) MASTER BATHROOM (OUTSIDE OF WATER |
| | CLOSET) WILL NEED AN EXHAUST FAN,PER |
| | 2004 FBC/M 402.3.1 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |