| Plan Review Notes For Permit 06021280 |
| Permit Number |
06021280 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-08 00:00:00 | | | | | | | PROVISO | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW PRIOR TO ROUGH INSPECTION. ALLOW | | | 2 WEEKS TO COMPLETE THE REVIEW PROCESS | | | FROM TIME OF SUBMITTAL. | | | | | | 1} THE GROUNDING ELECTRODE SYSTEM MUST | | | COMPLY WITH 250.52(A)(1) THROUGH (A)(6), | | | INDICATE ELECTRODES AVAILABLE BEING | | | USED.(IG: FOOTER STEEL) | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE SIZED PER 250.66.(#2 MINIMUM.) | | | | | | 3) THE KITCHEN COUNTERTOP RECEPTACLES | | | MUST COMPLY WITH 210.8(A)(7). | | | | | | 4} THE LAUNDRY RECEPTACLE MUST BE GFI | | | PROTECTED PER 210.8(A)(7). | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|