Plan Review Notes
Plan Review Notes For Permit 06021267
Permit Number 06021267
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-21 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- ARCHITECT TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTES AND 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. SEE
 ATTACHED COPY.
  
 3- ARCHITECT TO SPECIFY BUILDING CODE
 AND DESIGN CRITERIA USED. EG: MPH WIND
 LOAD, ENCLOSED OR OPEN STRUCTURE, ETC.
 SEC. R301 2004 RESIDENTIAL CODE.
  
 4- TWIST STRAP MTS18 SPECIFIED TO FASTEN
 2X6 RAFTER TO EXISTING CONCRETE BEAM IS
 A WOOD TO WOOD CONNECTOR. NEED TO
 SPECIFY WOOD TO MASONRY CONNECTOR. SEE
 SIMPSON CATALOGUE FOR PROPER MASONRY
 CONNECTORS AND SPECIFY FASTENERS AS
 TESTED AND PUBLISHED BY MANUFACTURER.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS AND CALCS FOR TYPE AND NUMBER
 OF FASTENERS THAT DIFFER FROM THOSE
 PUBLISHED BY MANUFAFCTURER. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 5- FLAT ROOF PRODUCT APPROVAL:
 A) CLEARLY SPECIFY WHICH OF THE
 APPROVED FLAT ROOF ASSEMBLIES IS GOING
 TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH GENERAL LIMITATION #7 OR #9.
 B) IF LIMITATION #7 APPLIES, THEN
 PROVIDE COMPLETE CALCULATIONS DONE BY
 ANY OF THEPROFESSIONALS SPECIFIED ON
 LIMITATION #7.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR THE SIMPSON STRUCTURAL
 CONNECTORS SPECIFIED ON PLANS AS
 REQUIRED BY RULE 9B-72 OF DEPARMENT OF
 COMMNUNITY AFFAIRS. GO TO
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION AND DOWNLOAD PRODUCT
 APPROVALS.
  
 7- ARCHITECT TO REVIEW AND APPROVE IN
 WRITTING (TYP. DONE BY USING STANDARD
 REVIEW STAMP) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 8- CONTRACTOR TO UPDATE INSURANCE. IT
 EXPIRED ON 2-28-06.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved