2006-08-28 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- ENGINEERING FIRM MUST PROVIDE THE
 CERTIFICAATE OF AUTHORIZATION NUMBER IN
 THE SOIL TEST REPORT AS REQUIRED BY SEC.
 61G15-23.002 OF THE FLORIDA
 ADMINISTRATIVE CODE.
 ***REQUESTED ON PREVIOUS CHECKLIST AND
 NOT DONE.
  
 2- AS REQUIRED BY DCA RULE 9B-72,
 PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) POCKET SLIDING GLASS DOORS AS SHOWN
 ON PLANS. INFORMATION SUBMITTED DOESN'T
 HAVE ANY DRAWINGS.
  
 B) ENGINEER TO CLARIFY WHY APPROVING
 THESE SLIDING GLASS DOORS IF THERE ARE
 NOT DRAWINGS SHOWING SPECIFIC SLIDING
 GLASS DOORS AND THE DESIGN PRESSURES
 THEY WERE DESIGNED FOR).
  
 3- STORM SHUTTERS:
 A) STRUCTURE TO BE ATTACHED TO IS
 CONCRETE BLOCK NOT CONCRETE. REVISE
 ANCHOR SPACING AS REQUIRED. SEE
 INSTALLATION SCHEDULE SHOWN ON
 ENGINEERED DRAWINGS FOR ANCHOR SPACING
 ACCORDING TO THE DESIGN PRESSURES AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE
 BLOCK). AND, REVISE INSTALLATION
 SCHEDULE AS REQUIRED.
 ***NOTE: THERE IS NOT SUCH THING AS
 SOLID CONRETE BLOCK. PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR SOLID CONCRETE
 BLOCK INSTALLATIONS. SEE SHUTTERS
 ENGINEERED DRAWINGS.
  
 4- CONTRACTOR TO UPDATE LICENSE RECORDS.
 ACCORDING TO THE STATE RECORDS, LICENSE
 # CGC059256 IS FOR WELLINGTON EQUESTRIAN
 DEVELOPMENT. PERMIT APPLICATION SAYS NEW
 ENGLAND BUILDERS. NEED TO CORRECT
 INFORMATION TO MATCH.
  
 5- ENERGY CALCULATIONS:
 A) SEE MECHANICAL PLAN REVIEWER
 COMMENTS AND REVISE AS REQUIRED.
  
 B) CALCULATIONS NEED TO BE DONE FOR
 WORST CASE SCENARIO OR MUST BE DONE FOR
 CORRECT HOUSING ORIENTATION.
 CALCULATIONS DON'T COMPLY WITH EITHER
 ONE. SEE SURVEY FOR CORRECT HOUSE
 ORIENTAION AND REVISE AS REQUIRED.
  
 C) REVISE OVERHANG LENGHT AND HEIGHT.
 SEE SEC. 13-601 FBC 2004 FOR CORRECT WAY
 OF CALCULATING OVERHANG LENGTH AND
 HEIGHT AND REVISE CALCULATIONS AS
 REQUIRED.
  
 D) PROVIDE COMPLETE ADDRESS AND OWNER
 INFORMATION.
  
 E) REVISE NAME OF CONTRACTOR. SEE ITEM
 #4 ABOVE.
  
 6- NEED TO REVISE NOTICE OF COMMENCEMENT
 WITH CORRECT CONTRACTOR'S NAME. SEE ITEM
 #4 ABOVE.
 ALSO, NOC IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT STARTED. SEC. 713.13(2)
 FLORIDA STATUTES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712