| Plan Review Notes For Permit 06021248 |
| Permit Number |
06021248 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-23 00:00:00 | DENIED; | | | NO CHANGES TO THE SANITARY RISER DIAGRAM | | | SINCE LAST REVIEW. | | | 1.FLOOR PLAN DOES NOT MATCH SANITARY | | | RISER DIAGRAM. THERE IS NO BATHROOM #2 | | | ON FLOOR PLAN, BUT THERE IS ON RISER | | | DIAGRAM. | | | 2.HORIZONTAL DRY VENTS ARE NOT PERMITED | | | IN THE DRAINAGE SYSTEM, MASTER BATH | | | HERS, SEC 905.3. | | | 3.BIDET IN HIS BATH IS NOT VENTED. | | | 4.THE BRANCH DRAIN FOR THE AUTOMATIC | | | CLOTHES WASHER IS REQUIRED TO BE 3" | | | SEC.403.6. | | | 5.CABANA BATH; SINK SHOWN ON RISER | | | DIAGRAM NOT SHOWN ON FLOOR PLAN. | | | SEE ONE SET OF PLANS MARKED IN RED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|