Plan Review Notes
Plan Review Notes For Permit 06021248
Permit Number 06021248
Review Stop P
Sequence Number 3
Notes
Date Text
2006-08-23 00:00:00DENIED;
 NO CHANGES TO THE SANITARY RISER DIAGRAM
 SINCE LAST REVIEW.
 1.FLOOR PLAN DOES NOT MATCH SANITARY
 RISER DIAGRAM. THERE IS NO BATHROOM #2
 ON FLOOR PLAN, BUT THERE IS ON RISER
 DIAGRAM.
 2.HORIZONTAL DRY VENTS ARE NOT PERMITED
 IN THE DRAINAGE SYSTEM, MASTER BATH
 HERS, SEC 905.3.
 3.BIDET IN HIS BATH IS NOT VENTED.
 4.THE BRANCH DRAIN FOR THE AUTOMATIC
 CLOTHES WASHER IS REQUIRED TO BE 3"
 SEC.403.6.
 5.CABANA BATH; SINK SHOWN ON RISER
 DIAGRAM NOT SHOWN ON FLOOR PLAN.
 SEE ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695