| 2006-08-14 00:00:00 | *** DENIED *** |
| | 1) SEE ENERGY CALCULATIONS HEATER 13A |
| | EQUALS 2.45 KW, HEATER B&C EQUALS 7.3 |
| | KW, MECHANICAL PLANS ARE SHOWING 10 KW |
| | AND TWO 5 KW, PLEASE CORRECT ENERGY |
| | CAL'S.. |
| | |
| | 2) ENERGY CALCULATIONS NEED A WET |
| | SINGATUER ON THEM NOT A PHOTO COPY. |
| | |
| | 3) SEE MANUAL J CALCULATIONS SYSTEM ONE, |
| | CHECK SQUARE FOOTAGE, IF NOT CORREST FOR |
| | THE ZONE THEN PLEASE CORRECT. |
| | |
| | 4)SEE MANUAL J CALCULATIONS 2 SYSTEMS, |
| | THESE CALCULATIONS CAN NOT BE FOR THE |
| | TWO ZONES AS THE SQUARE FOOTAGE AND |
| | DESIGN ARE NOT THE SAME FOR THESE ZONES. |
| | |
| | 5) SEE MANUAL J CAL'S. 2 SYSTEMS AREA |
| | AND VOLUME 15,000 DIVIDEND BY 881 EQUALS |
| | A CEILING HIGHT OF 17 FEET, PLEASE |
| | CORRECT. |
| | |
| | 6) SEE MANUAL J CAL'S AREA 2388 + 881= |
| | 3269 SQ. FEET. BUILDING PLANS SHOW FIRST |
| | FLOOR AT 3234.5 SQ. FEET, PLEASE |
| | RECALCULATE MANUAL J'S. |
| | |
| | 7) ALL CHANGES TO PLANS NEED TO BE |
| | SIGNED AND DATED AT EACH CHANGE OR |
| | RECOPIED. |
| | |
| | 8) IS THE LOFT ON THE SECOND FLOOR GOING |
| | TO HAVE A/C, IF SO PLEASE ADD TO PLANS. |
| | |
| | 9) CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 |
| | . |
| | |
| | 10) ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |