Plan Review Notes
Plan Review Notes For Permit 06021248
Permit Number 06021248
Review Stop B
Sequence Number 3
Notes
Date Text
2006-07-03 00:00:001- PROVIDE COPY OF IMPACT FEES PAID
 RECEIPT. NOT PROVIDED WITH SUBMITTAL.
 PLEASE MAKE SURE REVISED DRAWINGS HAVE
 IMPACT FEES STAMP WHEN RE-SUBMITTING
 PLANS.
  
 2- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 PRODUCT APPROVAL IS TO VERIFY THAT
 PRODUCT MEETS THE DESIGN CRITERIA
 SPECIFIED BY THE DESIGNER. DESIGNER
 STILL NEEDS TO SPECIFY METHOD OF
 ATTACHMENT.
  
 3- SOIL TEST REPORT NEEDS:
 A) CERTIFICATE OF AUTHORIZATION IN THE
 LETTER HEAD OR TITLE BLOCK AS REQUIRED
 BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
 B) ORIGINAL SIGNATURE. NO COPY. SEC.
 61G15-23.002 F.A.C.
 C) REVISE CODE SPECIFIED. NEED TO REFER
 TO FBC 2004 NOT 2001.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR:
 A) POCKET SLIDING GLASS DOORS AS SHOWN
 ON PLANS. ONE SUBMITTED DOESN'T MATCH
 DOORS SHOWN ON PLANS.
 B) SINGLE HUNG WINDOWS. PROVIDE CURRENT
 NOA THAT MATCHES ONE SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL. GO TO THE DCA
 WEBSITE WWW.FLORIDABUILDING.ORG TO
 DOWNLOAD CORRECT NOA.
 C) FRENCH DOORS. PROVIDE NOA THAT
 MATCHES ONE SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL.SEE DCA WEBSITE ABOVE
 TO DOWNLOAD CORRECT NOA.
 D) FIXED WINDOWS. NEED MATCHING NOA
 ALSO. SEE COMMENTS ABOVE.
  
 5- PROVIDE APPROVED LISTING AND SPECS
 FOR EXTERIOR HOOD ABOVE BBQ GRILL. ONE
 SUBMITTED DOESN'T LIST THE HOOD FOR
 EXTERIOR INSTALLATION. HOOD MUST BE
 SPECIFICALLY DESIGNED FOR OUTDOOR USE.
  
 6- STORM SHUTTERS:
 A) PRODUCT APPROVAL DRAWINGS ARE NOT
 LEGIBLE. PROVIDE CLEAR & LEGIBLE DWGS.
 B) SPECIFY WHICH PANELS ARE TO BE USED.
 22 OR 24 GAUGE TO VERIFY COMPLIANCE WITH
 PANEL SPANS, ETC.
 C) MINIMUM PANEL SPAN TO BE 48". SEE
 PAGE 3 OF DRAWINGS AND REVISE OPENINGS 4
 AND 5 AS REQUIRED. THEY ARE 40" LONG.
 D) STRUCTURE TO BE ATTACHED IS CONCRETE
 BLOCK NOTCONCRETE. REVISE AS REQUIRED.
 E) REVISE ANCHOR SPACING FOR PANELS
 THAT ARE LARGER THAN 72". SEE ANCHOR
 SCHEDULE IN DRAWINGS.
  
 7- A) REVISE ROOF SHEATHING FASTENER
 SPACING. SEE TABLE 2304.9.1 FBC 2004 FOR
 FASTENER SPACING IN ROOF ZONE #3.
 B) REVISE DRAWING 1/8. ROOF SHEATHING
 INFORMATION TO MATCH.
  
  
 NOTE:
 WHEN RE-SUBMITTING PACKAGE, PLEASE PUT
 TOGETHER 2 COMPLETE SETS. DRAWINGS 1
 THRU 16.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.